Bürkert 8792 Extra instructies - Pagina 5

Blader online of download pdf Extra instructies voor {categorie_naam} Bürkert 8792. Bürkert 8792 12 pagina's. Position controller and process controller with ii 3g ex ec ic iic t4 gc / ii 3d ex tc iiic t135c dc approval
Ook voor Bürkert 8792: Montagehandleiding (16 pagina's), Montagehandleiding (16 pagina's)

Bürkert 8792 Extra instructies
BVS 16 ATEX E 118 X

Authorized use

3
AUTHORIZED USE
Non-authorized use of the device may be dangerous to
people, nearby equipment and the environment.
▶ The device is designed to be mounted on pneumatic lifting
and rotary actuators for the control and regulation of media.
Type 8791 to 8793 PX45 is approved according to device
group II category 3G/D for use in explosion-risk areas of
Zones 2 and 22. The complete identification is located on the
type label (see chapter "5.4").
▶ The device is mounted on a pneumatic lifting or rotary actua-
tor. In doing so, the control valve must have at least explosion
protection approval of the position/process controller.
▶ During use observe the permitted data, the operating condi-
tions and conditions of use specified in the contract docu-
ments, the operating instructions and on the type label
- of the position/process controller and
- the control valve.
▶ Use the device only in conjunction with third-party devices
and components recommended and authorized by Bürkert.
▶ Correct transportation, storage and installation as well as care-
ful operation and maintenance are essential for reliable and
fault-free operation.
▶ Use the device only for its intended purpose.
4
PARTICULAR SAFETY
INSTRUCTIONS
DANGER!
Risk of explosion when removing the electric circular plug.
▶ Secure cable connections, which use circular plugs, with
suitable locking clips. This will prevent the circular plug from
working loose.
For example: EXCLIP, FA. Phoenix Contact,
Type SAC-M12-EXCLIP-M, art. no. 1558988 or
Type SAC-M12-EXCLIP-F, art. no. 1558991
or locking clips, FA. ESCHA
Locking clip M8 x 1, art. no. 8040691
Locking clip M12 x 1, art. no. 8040501.
▶ Do not remove or connect electric circular plug until the power
supply has been disconnected.
Risk of explosion when opening the device.
▶ Open device only when no explosive atmosphere is present.
Risk of explosion caused by electrostatic discharge.
In the event of a sudden discharge from electrostatically
charged devices or individuals, there is a risk of explosion in
the potentially explosive atmosphere.
▶ Protect device from large charge-generating processes.
▶ Ground housing before start-up.
▶ Take suitable measures to ensure that no electrostatic dis-
charges can build up in the potentially explosive atmosphere.
▶ Clean the device surface by gently wiping it with a damp or
anti-static cloth only.
english
5