Chromalox GXF Series Installatie-instructies
Blader online of download pdf Installatie-instructies voor {categorie_naam} Chromalox GXF Series. Chromalox GXF Series 4 pagina's. Grounded teflon immersion heaters
Installation Instructions
Chromalox
Grounded Teflon
GXF/GXFL
FIRE/EXPLOSION HAZARD: This heater is not
intended for use in hazardous atmospheres where
flammable vapors, gases, liquids, or other com-
bustible atmospheres are present as defined in
the National Electrical Code. Failure to comply can
result in explosion or fire.
Chromalox type GTF series of Teflon
sion heaters are especially suited for most plating tank and other
corrosive solutions. It is inert to acid baths, anodizing and picking
operations up to 212˚F solution temperatures.
Sheath corrosion can result in a ground fault
which, depending upon the solution being heated,
can cause an explosion or fire.
IMPORTANT: It is the responsibility of the pur-
chaser of the heater to make the ultimate choice
of sheath material based upon his knowledge of
the chemical composition of the corrosive solu-
tion, character of the materials entering the solu-
tion, and controls which he maintains on the
process. Chromalox cannot warrant any electric immersion
heater against failure by sheath corrosion if such failure is the
result of operating conditions beyond our control.
© 2010 Chromalox, Inc.
Chromalox
®
Type GXF/GTF/GTFL Series
®
over-the-side immer-
®
SERVICE REFERENCE
DIVISION
SALES
REFERENCE
DATE
Immersion Heaters
®
GTF
GENERAL
1. Heater Construction Characteristics
A. High quality resistance wire held in place by compacted mag-
nesium oxide in stainless steel sheath and Teflon
B. Low watt density.
C. Grounded construction.
D. Over-temperature protection.
E. Epoxy filled, vapor tight, plastic terminal enclosure prevents
entry of contaminants.
F. Flexible conduit 3' long with 6" leadwire extension is stan-
dard.
The system designer is responsible for the safety
of this equipment and should install adequate
back-up controls and safety devices with their
electric heating equipment. Where the conse-
quences of failure could result in personal injury
or property damage, back-up controls are essen-
tial.
4
GTF
SECTION
(Supersedes PD444-1)
161-562652-001
DECEMBER, 2004
GTFL3
* Teflon
®
is a registered trademark of DuPont Co.
PD444-2
GTF6
®
covered.