Chtce ZHRV2-54T Gebruiksaanwijzing
Blader online of download pdf Gebruiksaanwijzing voor {categorie_naam} Chtce ZHRV2-54T. Chtce ZHRV2-54T 2 pagina's. Digital household self-resetting overvoltage and undervoltage protector
R
Operating Instruction of ZHRV2-54T Digital Household Self-resetting Overvoltage and Undervoltage Protector
Functions and features
Built-in high-performance microcontroller, with high
reliability and strong antijamming capability.
LED Nixie tube displaying the operating voltage value.
Featuring with overvoltage and undervoltage protective function.
User can set the protection parameters by using the buttons.
Voltage measuring accuracy≤1%.
Measuring frequency: 45Hz-65Hz.
It can be installed on standard rail 35mm.
Model and meaning
Z H
RV2 54 T
Rated operational current: 50A, 63A,80A
Protection model
Voltage protection
Enterprise code
Main technical parameters
AC220V
Rated supply voltage
AC100V~400V
Rated operational voltage
Rated supply frequency
50/60Hz
Overvoltage actuation time
0.1s
120~200V,1s
Undervoltage
actuation time
<120V,<0.1s
5V
Voltage lagged value
≤1% (entire setting range)
Voltage measuring error
±10%+0.1s
Delay error
1%, true virtual value measurement
Measuring accuracy
415V
Rated insulation voltage
Model and maximum
rating
NT00-6A
of short circuit protector
IP20
Protection class
3
Pollution level
5
Electrical life
10
6
Mechanical life
10
≤2000m
Altitude
Operating ambient
-5℃~40℃
temperature
≤50% (40℃) (without condensation)
Permissible relative humidity
-25℃~55℃
Storage temperature
Technical parameters
Setting range
Stepping amount
~
210V
280V
Overvoltage operating value
~
Undervoltage operating value
120V
200V
~
5s
600s
Breakover delay time
Current specification
50A
Maximum operating current
50A
(within 10min)
Rated operating frequency
10kW
Maximum cross-section
16mm 2
of conductor
Operating instructions of button menu
○
Panel schematic diagram
Factory set value
1V
250V
1V
170V
5s
15s
63A
80A
63A
80A
13kW
17kW
2
2
16mm
16mm
R
LED Nixie tube
Button explanation
Setting of overvoltage operating value/digit+ button
Confirm modification button
Setting of Undervoltage operating value/digit- button
Example
Breakover delay display
Operating voltage value of LED Nixie tube flickers during breakover
delay; operating voltage value of LED Nixie tube will be normally on
after delay is over and output relay is with breakover.
Setting of overvoltage operating value
Long press
for 3s to enter setting interface of Undervoltage operating value:
The rightmost indication point flickers after entering overvoltage setting interface.
It can change the setting value by pressing
The relay will automatically quit the menu and not save the modified
data if not operating the button for continuous 60s during setting
parameters.
Setting of Undervoltage operating value
Long press
for 3s to enter setting interface of Undervoltage operating value:
-1-
Conform to:IEC60947-5-1standard
Long press for 3s
Flickers
Confirm modification
Long press for 3s
Flickers
Confirm modification