AQUATECH AquaBreak AB5 Instructies voor - Pagina 10

Blader online of download pdf Instructies voor voor {categorie_naam} AQUATECH AquaBreak AB5. AQUATECH AquaBreak AB5 18 pagina's. Breaktank & pumpset for backflow protection to fluid category 5

 
Fig. 1.5a & b Isolation valve on pipework & Flexible hose with drain cock on vessel (non‐flow through vessel 
shown) 
 
1.3.5 
FLOW THROUGH VESSELS 
Some installations require flow through vessel(s) supplied loose for site fitting into the discharge pipework via a 
flowjet isolation and drain valve. The number and size of vessels supplied varies according to site conditions. 
Ensure "O‐ring" is in place inside valve to prevent leakage. 
 
Fig. 1.6a & b Fit flow through vessel into discharge system pipework flowjet valve. 
Set up the vessel so the air charge filling valve (top) is accessible for future maintenance. All vessels must have 
isolating and drain off valves fitted to enable them to be serviced. 
Set the air cushion pre‐charge pressure to the correct level (see section 2.4), dependent on the application 
required for the vessel. Refer to the Operating parameters at the back of this manual or contact Aquatech‐
Pressmain for advice. 
 
1.3.6 
ELECTRICAL 
WARNING: DO NOT TOUCH ANY LIVE PARTS FOR AT LEAST 5 MINUTES AFTER SWITCHING 
OFF THE POWER TO ALLOW CAPACITORS TO DISCHARGE 
 
READ GENERAL SAFETY INFORMATION 0.0, WARNINGS 0.1 and CAUTIONS 0.2, 0.3 & 0.4 
1.3.6.1 
All wiring must comply with the latest edition of local wiring Regulations. 
1.3.6.2 
Wear anti‐static wrist strap at all times to avoid static discharge causing problems with the built in 
electronic program. 
1.3.6.3 
Connect incoming electrical mains supply to identified terminals on isolator IS1 in control panel (see 
fig. 1.7). Ensure voltages and frequency indicated on the motor nameplates and wiring diagrams 
correspond with supply mains data and that the supply fuse type & rating is correct for the total 
current rating of the equipment. 
1.3.6.4 
Complete any required earth bonding. 
 
AquaTech-Pressmain Instruction Manual\AquaBreak
 
 
 
AquaBreak Series  
 