Installation

Installing Tank Unit
1
Choose location for Tank Unit on the top of the tank or cistern, close to an
inspection hatch is best in case you need to adjust the sensor cone.
Ideal. Mount within
reach of access hole
For tanks less than 1500mm (5') it's best to deep mount unit in center of tank
2
Drill a 50mm (2") hole in tank.
For thick concrete tanks make
a 75mm (3") hole.
3
Measure the depth of
tank to the base (or to the
water outlet). Write this
measurement down.
4
Insert Tank Unit in hole and
rotate so tank antenna is on
the lower side (to prevent
water entering unit). Ensure
that the transducer cone
underneath is pointing
directly at the surface of the
water.
For plastic tanks use the supplied screws to attach the Tank Unit to the tank.
For metal tanks first drill 3mm or ¼" holes, and then fasten using the screws.
For concrete tanks drill 6mm or ¼" holes, insert the supplied plastic plugs and then
fasten using the screws. IMPORTANT NOTICE: Do not over tighten screws when
fastening to tank unit to the tank top, as this may cause the housing to split.
Incorrect. Mount unit
away from ribbed walls
to prevent signal
reflection off walls
8
– 3 –
C orrect. For buried
tanks mount unit in
center of lid, or on
bracket mounted in riser
M107
Antenna should be
mounted on the
opposite side
Transducer is not
pointing at the
surface of the water
Water will not enter
antenna hole
Transducer is parallel
to water