Long Term Relaxation Period (LTRP) – REST MODE
The system enters this state of operation as soon as FILTRATION is finished, there is no effluent being discharges during LTRP mode, the system's
BLUE FLOAT
will be in the
DOWN
BLOWER:
DISCHARGE PUMP:
STATE:
Filtration Time:
Rest Time:
BLOWER TIMER FEATURE-SFR
While in LTRP the blower is cycled ON and OFF, this is the SFR feature. The default SFR timer setting is for 30 mins ON/ 90 mins OFF. Please
contact the factory to adjust the timer.
MANUAL MODE
Manual mode allows the operator to manually run the BioBarrier's components regardless of the float position. To get the system into
MANUAL mode, Press
button multiple times to reach MODE in the "Setting / Information" screen. To change the MODE press the right arrow
key
, the cursors will move to the next screen (AUTO), use the up
desired mode press the "Ok" button to save.
IN MANUAL MODE
Turn blower ON and OFF by pressing the BLOWER ON/OFF button. The discharge pump can be switched ON and OFF by pressing the
DISCHARGE PUMP ON/OFF button. DO NOT run the discharge pump manually for longer than 3 minutes. The optional sludge mixing
pump can be manually run by depressing the MIXING PUMP ON/OFF button.
CERTIFICATIONS
0.5, 1.0, and 1.5 systems are NSF/ANSI Standard 40 (Class I), 245
®
BioBarrier
(nitrogen reduction), and 350 (class R water reuse) tested/ certified to:
COLLECTION OF EFFLUENT SAMPLE
If an effluent sample is required for regulatory purposes, it should be collected at a point
in the BioBarrier® pump discharge line as close to the pump as is feasible. For
guidance, please ask for the "Testing Protocol" document. If an effluent sample is
required, follow this recommended procedure:
1. Collect it at a free falling point after the discharge from the BioBarrier
2. All samples must be collected, stored, transported and tested according to the most current version of Standard Methods.
3. A sample can be collected while the system is in AUTOMATIC MODE/ ACTIVE FILTRATION or in Manual mode.
position. The system's component's operations are:
On Timer (30 Min. ON – 90 Min OFF)
Always ON
LTRP (Displayed)
Showing how long it took the system to
filter the last batch.
Showing how long the system has been
resting (HH:MM), and it is counting.
®
01/01/01
LTRP
or down
arrow to change the mode to (MANUAL). Once you set the
PARAMETER
CBOD5
TSS
pH
Total Nitrogen
system OR from the outlet piping of the filtrate pump.
®
00:00
OK
00:02
04:38
NSF LIMIT
30 day avg.
25 mg/L
7 day avg.
40 mg/L
30 day avg.
30 mg/L
7 day avg.
45 mg/L
6-9 s.u.
50% reduction of influent
AUTO