BE005/BE007 Corridor Bells: Locate BE005 and BE007 Cor-
ridor Bells in corridor above door height. Location in corridor
will be determined by the number of bells required on each
floor.
SS106 Transformer: Locate SS106 in an accessible area near a
source of 117 VAC. Observe local codes.
Wiring Installation
Run wiring conduit from corridor light to corridor light and
terminate at the CM800 or CM900 annunciator panel. Select
conduit size according to the application, as shown in wiring
diagrams in this booklet. Observe local codes.
PK2019, PK2019A Options:
• For 30-second delay before tone, connect terminal A to
terminal N.
• For steady tone, connect terminal W to terminal N. If the
annunciator lamp is flashing, the tone will be intermittent
despite terminal W connection.
Housing Installation
CM800, CM900 Annunciators:
Flush Wall Mount—Provide a wall cutout as shown in
Figure 1. Fit the back box and frame assembly into the
prepared opening. Fasten the assembly in place. Note: The
back box must be TekTone
Surface Wall Mount—Fasten the back box and frame
assembly to the wall through the holes provided in back of
the box, using suitable fasteners. Note: Back box must be
®
TekTone
OH300 Series.
SF117 series, SF118 series, SF154 Emergency Call Stations:
Install single gang ring (or single gang ring and double gang
box) as shown in Figure 2 for each emergency call station
in system. Minimum dimensions of back box must not be less
than 4"×4"×1.5". Minimum opening on ring must not be less
than 1.75"×2.75". Minimum clearance from live parts of the
station to dead metal parts must not be less than 0.5".
Page 2 • IL514 CM800/CM900 Emergency Call System Manual
®
OH200 Series.
IR019, IR019B Remote Annunciator Tone Speakers: Install
double gang ring (or double gang ring and double gang box)
as shown in Figure 3 for each tone speaker station. Mini-
mum dimensions of back box must not be less than
4"×4"×1.5".
LI118B, LI123B Corridor Lights: Install double gang ring (or
double gang ring and double gang box) as shown in Fig-
ure 3 for each tone speaker station. Minimum dimensions of
back box must not be less than 4"×4"×1.75".
LI381, LI382 Corridor Lights: Install double gang ring (or
double gang ring and double gang box) as shown in Fig-
ure 3 for each corridor light. Minimum dimensions of back
box must not be less than 4"×4"×1.5". Minimum opening on
ring must not be less than 2.75"×2.75". Minimum clearance
from live parts of the station to dead metal parts must not be
less than 0.5".
LI382LED Corridor Zone Light: Install standard one- or two-
gang box with one- or two-gang ring as shown in Figure 3
for each tone speaker station. Minimum clearance from live
parts of the station to dead metal parts must not be less than
0.5".
BE005, BE007 Corridor Bells: Install a standard 4" Bell Box.
Wire Checkout
Use an ohmmeter or other continuity checking device to test
wires for shorts or grounds. If shorts or grounds are
encountered, find and correct the problems before continuing.
Make sure the minimum number of conductors that are needed
for all of the equipment being used in the system are available.
Connections Checkout
Re-check all connections to equipment. If all wires and
connections are satisfactory, connect the primary coil of the
SS106 Transformer to a source of 117 VAC 60 Hz (30 VA max.).