Shift 1, Shift 2 and Shift 3 Pagers (Figure 9)
Enter a Pager ID for each of the message types and
shifts being used. Each shift has three Pager IDs:
The Active message is sent to the first Pager ID.
The Pulse 1 (slow pulse) message is sent to the
second (middle) Pager ID.
The Pulse 2 (fast pulse) message is sent to the third
Pager ID.
The Shift Schedule checkbox in the Global Settings
screen determines which shifts must have Pager IDs
assigned:
If you checked Shift Schedule in the Global Settings
screen, fill in Shift 1, Shift 2 and Shift 3 Pagers.
If you did not check Shift Schedule in the Global
Settings screen, fill in Shift 1 Pager.
Use this formula to convert the pager's CAP code to its
corresponding Pager ID (add leading zeros to make 7
digits): Pager ID = [(pager's CAP code × 8) + 10000]
If a shift's message type is not being used, enter 7 zeros
as its Pager ID.
Escalation Pagers (Figure 9)—These pagers are sent a call
if it is not reset within a certain period of time. Check the
box and enter a Pager ID for each of the shifts being used.
The first Pager ID is for shift 1, the second Pager ID is for
shift 2, and the third Pager ID is for shift 3.
Use this formula to convert the pager's CAP code to its
corresponding Pager ID (add leading zeros to make 7
digits): Pager ID = [(pager's CAP code × 8) + 10000]
If a shift is not being used, enter 7 zeros as its Pager ID.
Repeat—Choices are 0–5. Do not use the RUR setting
(Repeat until Reset), because it cancels escalations.
Interval—Choices are 2, 5, 10, 15, 20 or 30 minutes; and
1 or 2 hours.
Save Zone button—After all the fields have been completed
for the zone/input, click the Save Zone button at the top
right of the screen. Then begin programming the next
zone/input.
Figure 9—Assigning
Shift & Escalation Pagers
Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.
Simplified Contact Input Programming
Create one zone/input and click Save Zone. Then make a
copy of that zone/input using Save to Zone, and modify
just the fields that vary from zone/input to zone/input.
1. In the first field, enter the zone/input number to be copied.
In the second field, enter the zone/input number to be
created. For example, Save to Zone 2 to 32 copies all data
from zone/input 2 to zone/input 32.
2. Click Save to Zone. The screen will refresh and display
the newly created zone/input.
3. Make any changes necessary, and click Save Zone.
Modifying Contact Inputs—To modify existing zones/inputs:
1. Enter the zone/input number you want to edit in the Find
Zone box, and click Find Zone. The contact programming
information for the zone/input you entered will appear.
2. Make any changes necessary, and click Save Zone.
3. To modify the next zone/input, click Next to display it,
make any changes necessary, and click Save Zone.
Continue until all zones/inputs have been modified.

Print Database Button

The database report is a complete record of all currently
programmed zones/inputs on the master and attached slaves.
To create it, click the Print Database button at the bottom of
the Contact Input Programming screen. All the active zones/
inputs will be displayed in your web browser. Select File >
Print in the web browser to print the report.

Finishing up

1. Replace the covers on all NC377 Paging Interface Adapters.
2. Connect the master to the paging transmitter using the serial
cable supplied with the paging transmitter. Connect the
master and first slave using the gray crossover cable. Connect
all slaves together using the red patch cables.
3. Power up all NC377 Paging Interface Adapters.
4. Place calls from rooms to test all zones/inputs.
IL871 NC377 Paging Interface Adapter Manual • Page 7