take into consideration stack configuration and insure that the chimney
above deck is clear of any obstruction.
Chimney Pipe
The location and configuration of the chimney stack is very important to the
operation of the heater. A long, straight chimney stack will ensure a strong
draft for correct operation. The diameter of the chimney must be what is
specified. We recommend that the length of your chimney is a straight 5-6ft
run with a minimum of 4ft long and a maximum of 10ft. Avoid using elbows
and if necessary, use 45 degree elbows and allow for as much straight pipe
as possible with a minimum of 12" (28 cm) from the top of the heater. There
is no connector to connect the chimney pipe to the heater. There is a flue
collar already attached to the top of the heater and the pipe can attach by
squeezing the pipe into an oval shape and fitting it over the flue collar.
Chimney Pipe Diameter
3" diameter chimney (7.5cm)