2. General Regulations for Hold-Open System
In Germany, the installation of a hold-open system is regulated by the
general building inspection approval or type approval of the DIBt. For
European countries without national regulations, EN 14637 is used as
a guideline.
These regulations also govern:
-
the mounting positions and number of fire detectors
-
the position and design of the hand switch
-
the acceptance test (first placing in service) and marking
-
the recurring functional tests and maintenance
-
the requirements for the qualification of the persons testing
and maintaining
The documents are available under www.dictator.de. The general type
approval DIBt also includes all permissible device combinations.
For further instructions on installation, use, maintenance, functional
testing and servicing as well as documentation, please refer to our
operating manual for hold-open systems, which is available to our
authorised specialists for DICTATOR hold-open systems.
In the Ex-area a hand switch with appropriate explosion protection must
be used.
Only cables approved for this purpose may be used in the Ex-area (e.g.
Ölflex EB 2 x 0.75 mm²). The cross-section must be selected according
to the required cable length.
Depending on the application (must be clarified object-related), we re-
commend shielding the cables.
The device combinations "RZ-24" and "RZ-24-05" have to be
mounted in the detection range of one of the fire detectors of the
respective door. If not, an additional detector is required.
To ensure the correct functioning of the hold-open system, the DICTA-
TOR smoke and heat detectors have to be replaced after a maximum
of 8 years of operational life. In Germany the DIN 14677 regulates the
replacement obligation of fire detectors in hold-open systems.