9. Reinstall the Inverter Module, tighten the two thumbscrews and reconnect the front panel connections (tamper,
temperature sensor, battery harness, etc.).
10. For the DM3X, connect the Battery Sense Wire Kit (not required with Smart AlphaGuard). Refer to the battery
diagrams provided with the Sense Wire Kit or reference the DM3.0 Series Technical Manual (Alpha p/n 704-939-
B0).
11. For the DM3, ensure that the Smart AlphaGuard Wire Kit is connected on the left side of the XM3.
12. Verify the recording of the cable modem MAC address (RF MAC) by navigating to the XM3 Smart Display's
COMM Menu.
13. Connect the RF drop as shown in Fig. 5 for the DM3, or Fig. 6 for the DM3X. The DOCSIS specification for
downstream power level is ± 15 dBmV. However, for optimal performance, set the level as close to 0 dBmV as
possible. RF attenuators or cable simulators may be required to obtain optimal downstream and upstream RF
levels.
704-939-B1-001, Rev. A (09/2020)
Fig. 4, Completely Installed DM3X in XM3-HP
Tamper Switch Connector
Environmental (I/O) Connector
Ethernet Port
CAUTION!
A Ground Surge Protector is Required.
(Alpha p/n 162-028-10 or equivalent)
Fig. 5, DM3 Front Panel Connections
RF Cable to Headend