Ook voor ABB SACE Emax 2: Handmatig (5 pagina's), Handmatig (7 pagina's), Handmatig (6 pagina's), Handmatig (6 pagina's), Handmatig (5 pagina's), Handmatig (4 pagina's), Handmatig (4 pagina's), Handmatig (6 pagina's), Handmatig (4 pagina's), Handmatig (7 pagina's), Handmatig (6 pagina's), Gebruikershandleiding (10 pagina's), Handmatig (15 pagina's), Handmatig (4 pagina's), Handmatig (6 pagina's), Handmatig (5 pagina's), Handmatig (15 pagina's), Handmatig (4 pagina's), Handmatig (12 pagina's), Montage-instructies (20 pagina's), Handmatig (18 pagina's), Gebruikershandleiding (20 pagina's), Handmatig (16 pagina's), Snelstarthandleiding (7 pagina's), Montage (8 pagina's), Handmatig (11 pagina's), Vervanging (16 pagina's), Handmatig (14 pagina's), Handmatig (13 pagina's), Gebruikershandleiding (14 pagina's), Snelstarthandleiding (5 pagina's), Handmatig (4 pagina's), Handmatig (9 pagina's), Handleiding voor retrofitting (16 pagina's), Handmatig (11 pagina's), Handleiding voor retrofitting (10 pagina's)

ABB SACE Emax 2 Voorlopige gebruikshandleiding
15
- Operazione di TRIP TEST - TRIP TEST Operation
Prima della messa in servizio è possibile effettuare un TRIP TEST direttamente su sganciatore o da Ekip Connect
Per eseguire il test da sganciatore:
FASE
1
2
3
4
Per eseguire il test da Ekip Connect:
FASE
1
2
3
4
Ulteriori informazioni relative a Ekip Connect, Ekip TT e Ekip T&P sono reperibili sul sito http:
//www.abb.com/abblibrary/DownloadCenter/, in particolare con i documenti:
1SDH000891R0001 Ekip Connect
1SDH001000R0519 Ekip TT E1.2 - E2.2 - E4.2 - E6.2
1SDH001000R0517 Ekip T&P E1.2 - E2.2 - E4.2 - E6.2
Before commissioning it's possible to perform a TRIP TEST directly on the release or from Ekip Connect
To perform the test from release:
PHASE
1
2
3
4
To perform the test from Ekip Connect:
PHASE
1
2
3
4
Further information on Ekip Connect, Ekip TT and Ekip T&P are available from the web site http:
//www.abb.com/abblibrary/DownloadCenter/, in particular with the documents:
1SDH000891R0001 Ekip Connect
1SDH001000R0519 Ekip TT E1.2 - E2.2 - E4.2 - E6.2
1SDH001000R0517 Ekip T&P E1.2 - E2.2 - E4.2 - E6.2
For more information please contact:
ABB S.p.A.
ABB SACE Division
Via Pescaria, 5
24123 Bergamo - Italy
Phone: +39 035 395 111
©
Copyright 2014 ABB. All rights reserved.
www.abb.com

OPERAZIONE

Assicurarsi che l'interruttore sia chiuso e non siano presenti correnti primarie.
Collegare un modulo Ekip TT o Ekip T&P al connettore di test frontale.
Premere il pulsante iTest per almeno 9 secondi.
Verificare l'apertura dell'interruttore e la fuoriuscita del pulsante TU Reset.
OPERAZIONE
Assicurarsi che l'interruttore sia chiuso e non siano presenti correnti primarie.
Collegare un modulo Ekip T&P o Ekip Bluetooth al connettore di test frontale.
Avviare la comunicazione con Ekip Connect ed effettuare TRIP TEST.
Verificare l'apertura dell'interruttore e la fuoriuscita del pulsante TU Reset.
OPERATION
Make sure that the circuit-breaker is closed and that there are no primary currents.
Connect an Ekip TT or Ekip T&P module to the front test connector of frontal test.
Press the iTest push-button for at least 9 seconds.
Check that the circuit-breaker opens and that the TU Reset button comes out.
OPERATION
Make sure that the circuit-breaker is closed and that there are no primary currents.
Connect Ekip T&P or Ekip Bluetooth to the front test connector.
Start the communication with Ekip Connect and select Trip Test command.
Check that the circuit-breaker opens and that the TU Reset button comes out.