Accustat Independence ES-AH11 Gebruiksaanwijzing - Pagina 3

Blader online of download pdf Gebruiksaanwijzing voor {categorie_naam} Accustat Independence ES-AH11. Accustat Independence ES-AH11 3 pagina's.

Conventional System (Single Transformer)
Terminal
Block
Y1
G
RC
J3 Jumper
X
RH
W1
SW5 Settings:
Position 1, Not used
Position 2, Not used
Position 3, fan activity, OFF (fossil fuel),
ON (electric heat)
Position 4, differential, OFF (0.5°), ON (1.0°)
OFF
ON
Operating with a common wire connection:
If installing the thermostat with a common wire connection, place the
ENERGY HARVESTING switch in the OFF position. Upon first power
up or following a power failure the thermostat will run under normal
operating conditions within 5 minutes.
Operating without a common wire connection:
If installing the thermostat without a common wire connection, do the
following:
Prior to mounting the thermostat –
Place the ENERGY HARVESTING switch in the ON position.
At first power up or following a power failure it may take the thermostat
7 to 20 minutes for the power harvesting circuitry to charge before going
into the first heating or cooling call.
An optional method of bypassing the 7 to 20 minute wait is to connect
a 9V battery to the sensor board battery terminals.
LED D1 will light once the battery is connected.
When done charging the LED will become dim or go off (approximately
2 minutes).
Remove battery and the thermostat will run under normal operating
conditions within 5 minutes.
While the battery is attached the unit may be tested as stated to the
right.
NOTE: The thermostat will not attempt to control temperature
until the battery is removed
Stage 1 Cooling**
Fan
Cool System Power^
Common (optional)
Heat System Power^^
Stage 1 Heating¤
** For Y1 to be active, plug-in setpoint is required in C1 position
^ If dual transformers are used, the J3 jumper must be cut
^^ Only required if dual transformers are used.
For single transformer applications, it is not necessary to connect
RH. The J3 jumper must be connected.
¤ For H1 to be active, a plug in setpoint is required in H1 position
IMPORTANT NOTICE TO INSTALLERS TESTING:
To place thermostat in test mode insert 9 volt battery into sensor
board battery terminals.
If storage capacitors are not charged a light will come on in the upper
right corner.
NOTE: To test, plug-in setpoints are required.
Prior to the test verify that your SW5 switch settings are set correctly
per your application.
Cooling:
C1 setpoint must be installed.
HEAT/OFF/COOL switch must be in the COOL position.
1. Press the "B" button.
Fan (G) and cooling (Y1) will turn on.
2. Press the "B" button again.
All outputs will turn off and cooling test is complete.
Proceed to heating test, if necessary, or remove battery to end
testing.
Heating:
H1 setpoint must be installed.
HEAT/OFF/COOL switch must be in the HEAT position.
1. Press the "C" button.
Heat (W1) will turn on.
If SW5 switch position 3 is ON (electric heat) fan (G) will also turn on.
2. Press the "C" button again.
All outputs will turn off and heating test is complete.
Proceed to cooling test, if necessary, or remove battery to end
testing.
3
9510-0845 Rev A
11-11-09