Siemens SIMATIC ET 200AL Handmatig - Pagina 17

Blader online of download pdf Handmatig voor {categorie_naam} Siemens SIMATIC ET 200AL. Siemens SIMATIC ET 200AL 32 pagina's. 10-link digital output module dq 8x24vdc/2a 8xm12
Ook voor Siemens SIMATIC ET 200AL: Handmatig (38 pagina's), Handmatig (50 pagina's), Handmatig (38 pagina's), Handmatig (37 pagina's), Uitrustingshandleiding (46 pagina's), Handmatig (26 pagina's), Uitrustingshandleiding (28 pagina's), Uitrustingshandleiding (27 pagina's), Handmatig (25 pagina's)

Siemens SIMATIC ET 200AL Handmatig
Product overview
3.2 BusAdapter BA-Send 1xFC
3.2.3

Diagnostics by means of LED display

LED display
The figure below shows the LED display (status and fault display) of the BusAdapter BA-Send
1xFC.
Figure 3-4
Meaning of the LED display
The table below explains the meaning of the status and fault display.
DIAG LED
Table 3- 2
Status and fault display DIAG
DIAG LED
There is no connection between the ET-Connection
interface of the BusAdapter BA-Send 1xFC and the
Off
ET 200AL.
The CPU/interface module does not support the BA-
Send 1xFC.
There is a connection between the ET-Connection
interface of the BusAdapter BA-Send 1xFC and the
On
ET 200AL.
There is (at least) one diagnostics alarm of an ET-
Connection device. Group error for all ET-
Flashes
Connection bus nodes.
Set configuration does not match the actual
configuration on the ET-Connection.
16
DIAG (green/red)
LED display
Meaning
Remedy
Check whether the bus cable is interrupted.
Run a firmware update.
---
Check the ET-Connection device.
Check the configuration of the ET-Connection to
see whether a module is missing or defective, or
whether a non-configured module is wired.
Equipment Manual, 11/2020, A5E33344611-AD
Mixed configuration