Ook voor Siemens SIMATIC ET 200S: Gebruikershandleiding (18 pagina's), Handmatig (16 pagina's), Gebruikershandleiding (16 pagina's), Gebruikershandleiding (26 pagina's), Handmatig (37 pagina's), Handmatig (24 pagina's), Gebruiksaanwijzing (4 pagina's), Originele gebruiksaanwijzing (19 pagina's), Originele gebruiksaanwijzing (20 pagina's), Handmatig (34 pagina's), Handmatig (14 pagina's), Handmatig (24 pagina's), Originele gebruiksaanwijzing (17 pagina's), Originele gebruiksaanwijzing (19 pagina's), Handmatig (16 pagina's), Handmatig (28 pagina's), Handmatig (12 pagina's), Handmatig (32 pagina's), Handmatig (18 pagina's), Handmatig (12 pagina's), Handmatig (28 pagina's), Handmatig (22 pagina's), Handmatig (22 pagina's), Handmatig (36 pagina's), Handmatig (16 pagina's)

Siemens SIMATIC ET 200S Functiehandboek
Example: Start the motor at a specified speed
Proceed as follows to get the connected motor to turn at a speed of 500 rpm:
1. Enter the value "500" in the mySetpoint variable.
2. Set the myCommand variable to CMD_START in the symbol browser.
3. Start the command with myCmdExecute = TRUE.
The input parameter myFC_Control_In.setpoint is set to the speed parameterized in the
mySetpoint variable accordingly and transferred to the input parameter setpoint.
All enables in control word 1 are set. The motor starts to turn.
After the speed parameterized in the mySetpoint variable is reached, the command is ended
with myCmdDone = TRUE.
Note
When starting the motor with a rising edge on bit 0 in STW 1, bit 8 and bit 9 in STW 1 (jog
right/left) must have the signal level FALSE.
Assignment of ctrlDword (STW 1 and STW 2 of ET 200S FC) when starting the motor:
CMD_START
CMD_JOG_RIGHT : // motor jog. Right
CMD_JOG_LEFT
Example: Stop a running motor
Proceed as follows to stop a running motor:
1. Set the myCommand variable to CMD_STOP in the symbol browser.
2. Start the command with myCmdExecute = TRUE.
Bit 0 in control word 1 (On/Off) is reset. The motor begins to stop.
After reaching the actual speed < 1 rpm, the command is terminated with
myCmdDone = TRUE.
Note
Bit 0, bit 8, and bit 9 in STW 1 must have the signal level FALSE when stopping a motor.
Assignment of ctrlDword (STW 1 and STW 2 of ET 200S FC) when stopping the motor:
CMD_STOP
Supplement for the ET 200S frequency converter
Function Manual, 01/2015
: // start motor
: // motor jog. Left
:
// stop motor
Application example
5.2 Sequence of the application example
16#0000 047F hex or binary:
0000 0100 0111 1111
16#0000 057E hex or binary:
0000 0101 0111 1110
16#0000 067E hex or binary:
0000 0110 0111 1110
16#0000 047E hex or binary:
0000 0100 0111 1110
31