Siemens SIMATIC ET 200S Handmatig - Pagina 10

Blader online of download pdf Handmatig voor {categorie_naam} Siemens SIMATIC ET 200S. Siemens SIMATIC ET 200S 28 pagina's. Distributed i/o digital electronic module 4do dc24v/2a hf
Ook voor Siemens SIMATIC ET 200S: Gebruikershandleiding (18 pagina's), Handmatig (16 pagina's), Gebruikershandleiding (16 pagina's), Gebruikershandleiding (26 pagina's), Handmatig (37 pagina's), Handmatig (24 pagina's), Functiehandboek (40 pagina's), Gebruiksaanwijzing (4 pagina's), Originele gebruiksaanwijzing (19 pagina's), Originele gebruiksaanwijzing (20 pagina's), Handmatig (34 pagina's), Handmatig (14 pagina's), Handmatig (24 pagina's), Originele gebruiksaanwijzing (17 pagina's), Originele gebruiksaanwijzing (19 pagina's), Handmatig (16 pagina's), Handmatig (28 pagina's), Handmatig (12 pagina's), Handmatig (32 pagina's), Handmatig (18 pagina's), Handmatig (12 pagina's), Handmatig (22 pagina's), Handmatig (22 pagina's), Handmatig (36 pagina's), Handmatig (16 pagina's)

Siemens SIMATIC ET 200S Handmatig
Properties
1.1 2AI I 2WIRE HS analog electronic module (6ES7134-4GB52-0AB0)
Measuring principle
Cycle time/resolution:
Crosstalk between the inputs
Operational limit
(in the entire temperature range, with reference to
the input range)
Basic error limit (operational limit at 25°C with
reference to input range)
Temperature error (with reference to the input
range)
Linearity error (with reference to the input range)
Repeatability
(in steady state at 25°C with reference to input
range)
Number of outputs
Output voltage
Output current
Short-circuit protection
Input range (rated value/input resistance)
Connection of the sensors
Load of the 2-wire transducer
Permitted input current (destruction limit)
Smoothing of the measured values
With sensor supply voltage
1
For interface modules with process interrupt capability only
2
Parameter assignment error
3
Violation of low limit
Violation of high limit
Open circuit (only with 4 to 20 mA)
Process interrupt lost
10
Conversion time in µs (per channel)
Cycle time in ms (per module)
Resolution (including overrange)
With load
Rated value
Permitted range
Current
For current measurement as 2-wire
transducer
Analog value generation
SAR (Successive Approximation Register)
15 µs
0.25 ms
4 to 20 mA/15 bits
0 to 20 mA/15 bits
Interference suppression, error limits
> 50 dB
±0,3%
± 0,2 %
± 0.01 %/K
± 0,03 %
± 0,1 %
Sensor supply outputs
2
24 V (+5%/ -10%)
45 mA (per channel)
0 mA to 45 mA
Yes, electronic
Sensor selection data
4 to 20 mA/106 Ω
0 to 20 mA/106 Ω
Supported
max. 670 Ω
30 mA
Yes, can be assigned in 4 steps by means of
digital filtering
Step
None
Weak
Medium
Strong
2AI I 2WIRE HS analog electronic module (6ES7134-4GB52-0AB0)
Time constant
1 x cycle time
4 x cycle time
16 x cycle time
32 x cycle time
Manual, 01/2008, A5E01001734-02