Ook voor Siemens SIMATIC ET 200SP: Handmatig (40 pagina's), Gebruikershandleiding (21 pagina's), Handmatig (34 pagina's), Handmatig (48 pagina's), Handmatig (30 pagina's), Handmatig (34 pagina's), Productinformatie (38 pagina's), Handmatig (37 pagina's), Handmatig (36 pagina's), Handmatig (44 pagina's), Handmatig (31 pagina's), Handmatig (35 pagina's), Handmatig (23 pagina's), Configuratiehandleiding (20 pagina's), Handmatig (34 pagina's), Handmatig (29 pagina's), Handmatig (33 pagina's), Handmatig (31 pagina's), Gebruikershandleiding (32 pagina's), Handmatig (31 pagina's), Handmatig (28 pagina's), Handmatig (41 pagina's), Handmatig (49 pagina's), Handmatig (24 pagina's), Handmatig (34 pagina's), Handmatig (41 pagina's), Handmatig (30 pagina's), Handmatig (31 pagina's), Handmatig (27 pagina's), Handmatig (24 pagina's), Handmatig (24 pagina's), Handmatig (25 pagina's), Handmatig (49 pagina's), Handmatig (40 pagina's), Handmatig (38 pagina's), Handmatig (39 pagina's), Productinformatie (24 pagina's), Handmatig (32 pagina's), Productinformatie (10 pagina's), Uitrustingshandleiding (43 pagina's), Handmatig (33 pagina's), Uitrustingshandleiding (44 pagina's), Originele gebruiksaanwijzing (6 pagina's), Handmatig (35 pagina's), Handmatig (28 pagina's), Uitrustingshandleiding (32 pagina's), Handmatig (50 pagina's), Handmatig (30 pagina's), Handmatig (26 pagina's), Handmatig (28 pagina's), Handmatig (34 pagina's), Handmatig (44 pagina's), Handmatig (33 pagina's), Uitrustingshandleiding (42 pagina's), Originele handleiding (16 pagina's)

Siemens SIMATIC ET 200SP Handmatig
4.3

Address space

The module can be configured differently in STEP 7; see following table. Depending on the
configuration, additional/different addresses are assigned in the process image of the inputs.
Configuration options of RQ 4x120VDC-230VAC/5A NO ST
You can configure the module with STEP 7 (TIA Portal) or with a GSD file. If you configure
the module using a GSD file, the configurations are available under various short
designations/module names; see the table below. The following configurations are possible:
Table 4- 2
Configuration options with GSD file
Configuration
1 x 4-channel without
value status
1 x 4-channel with value
status
Evaluating the value status
An additional byte is allocated in the input address space if you enable the value status for
the digital module. Bits 0 to 3 in this byte are assigned to a channel. They provide
information about the validity of the digital value.
Bit = 1: No fault is present on the channel.
Bit = 0: Channel is disabled or there is a fault/error on the module.
If a fault/error occurs on a channel with this module, the value status for all channels is 0.
Address space
The following figure shows the assignment of the address space for the
RQ 4x120VDC-230VAC/5A NO ST with value status (Quality Information (QI)). The
addresses for the value status are only available if the value status is enabled.
Figure 4-1
Digital output module RQ 4x120VDC-230VAC/5A NO ST (6ES7132-6HD01-0BB1)
Manual, 09/2017, A5E03576775-AE
Short designation/module name in
the GSD file
RQ 4x120VDC-230VAC/5A NO
ST V0.0
RQ 4x120VDC-230VAC/5A NO
ST V0.0, QI
Address space of RQ 4×120VDC-230VAC/5A NO ST with value status
Configuration software, e.g. with STEP 7 (TIA Portal)
Integrated in hard-
ware catalog STEP 7
PROFINET IO
V14, SP1 or higher
with HSP 0222
V14, SP1 or higher
with HSP 0222
Parameters/address space
4.3 Address space
GSD file
GSD file
PROFIBUS DP
X
X
X
---
19