Ook voor Siemens SIMATIC ET 200SP: Handmatig (40 pagina's), Gebruikershandleiding (21 pagina's), Handmatig (34 pagina's), Handmatig (48 pagina's), Handmatig (30 pagina's), Handmatig (34 pagina's), Productinformatie (38 pagina's), Handmatig (37 pagina's), Handmatig (36 pagina's), Handmatig (44 pagina's), Handmatig (31 pagina's), Handmatig (35 pagina's), Handmatig (23 pagina's), Configuratiehandleiding (20 pagina's), Handmatig (34 pagina's), Handmatig (29 pagina's), Handmatig (33 pagina's), Handmatig (31 pagina's), Gebruikershandleiding (32 pagina's), Handmatig (31 pagina's), Handmatig (28 pagina's), Handmatig (41 pagina's), Handmatig (32 pagina's), Handmatig (49 pagina's), Handmatig (24 pagina's), Handmatig (34 pagina's), Handmatig (41 pagina's), Handmatig (30 pagina's), Handmatig (27 pagina's), Handmatig (24 pagina's), Handmatig (24 pagina's), Handmatig (25 pagina's), Handmatig (49 pagina's), Handmatig (40 pagina's), Handmatig (38 pagina's), Handmatig (39 pagina's), Productinformatie (24 pagina's), Handmatig (32 pagina's), Productinformatie (10 pagina's), Uitrustingshandleiding (43 pagina's), Handmatig (33 pagina's), Uitrustingshandleiding (44 pagina's), Originele gebruiksaanwijzing (6 pagina's), Handmatig (35 pagina's), Handmatig (28 pagina's), Uitrustingshandleiding (32 pagina's), Handmatig (50 pagina's), Handmatig (30 pagina's), Handmatig (26 pagina's), Handmatig (28 pagina's), Handmatig (34 pagina's), Handmatig (44 pagina's), Handmatig (33 pagina's), Uitrustingshandleiding (42 pagina's), Originele handleiding (16 pagina's)

Siemens SIMATIC ET 200SP Handmatig
Parameters
Input delay
Potential group
If you use a floating switch, you need to connect a resistor in parallel so that the wire break diagnostics is enabled in the
1
open state (sensor resistance for the wire break diagnostics: 25 kΩ to 45 kΩ).
Due to the limited number of parameters with a maximum of 244 bytes per ET 200SP station for a PROFIBUS GSD
2
configuration, the configuration options are restricted. If required, you can assign these parameters using data rec-
ord 128 as described in the "GSD file PROFINET IO" column (see table above). The parameter length of the I/O module
is 32 bytes.
Digital input module DI 16x24VDC ST (6ES7131-6BH01-0BA0)
Manual, 09/2017, A5E03573442-AF
Range of values
None
0.05 ms
0.1 ms
0.4 ms
0.8 ms
1.6 ms
3.2 ms
12.8 ms
20 ms
Use potential group of
the left module (mod-
ule plugged into a
dark-colored Ba-
seUnit)
Enable new potential
group (module
plugged into light-
colored BaseUnit)
Default
Parameter
reassignment
in RUN
3.2 ms
Yes
Use potential
No
group of the left
module
Parameters/address space
4.1 Parameters
Scope with configuration software,
e.g. STEP 7 (TIA Portal)
GSD file
GSD file
PROFINET IO
PROFIBUS DP
Channel
Module
Module
Module