Ook voor Siemens SIMATIC ET 200SP HA: Handmatig (32 pagina's), Handmatig (34 pagina's), Handmatig (38 pagina's), Uitrustingshandleiding (44 pagina's), Uitrustingshandleiding (50 pagina's), Uitrustingshandleiding (38 pagina's), Uitrustingshandleiding (46 pagina's), Uitrustingshandleiding (42 pagina's), Uitrustingshandleiding (44 pagina's), Uitrustingshandleiding (36 pagina's), Uitrustingshandleiding (38 pagina's)

Siemens SIMATIC ET 200SP HA Handmatig
Principle
The following figure gives you another graphic illustration of the principle of flutter monitoring.
Figure 4-2
Flutter monitoring and settling time when flutter error occurs
Does the monitoring time in the event of a fault restart as three monitoring windows if the signal
continues to change?
The signal changes...
once more than what is set in the number of signal changes. Monitoring time is restarted.
less often than what is set in the number of signal changes.
Digital Input Module DI 16xNAMUR HA (6DL1131-6TH00-0PH1)
Manual, 11/2017, A5E39293880-AB
The principle of flutter monitoring
Result
The monitoring time is not started again, in other words, the
monitoring time runs once after a flutter error is detected.
Even a change just before the time is up is tolerated.
Parameters
4.4 Flutter monitoring