Siemens SIMATIC ET 200SP HA Handmatig - Pagina 14

Blader online of download pdf Handmatig voor {categorie_naam} Siemens SIMATIC ET 200SP HA. Siemens SIMATIC ET 200SP HA 38 pagina's. Distributed i/o devices busadapter for distributed i/o
Ook voor Siemens SIMATIC ET 200SP HA: Handmatig (32 pagina's), Handmatig (50 pagina's), Handmatig (34 pagina's), Uitrustingshandleiding (44 pagina's), Uitrustingshandleiding (50 pagina's), Uitrustingshandleiding (38 pagina's), Uitrustingshandleiding (46 pagina's), Uitrustingshandleiding (42 pagina's), Uitrustingshandleiding (44 pagina's), Uitrustingshandleiding (36 pagina's), Uitrustingshandleiding (38 pagina's)

Siemens SIMATIC ET 200SP HA Handmatig
Parameters

4.2 Module/channel parameters

4.2
Module/channel parameters
Parameters of the DI 8x24...125VDC HA
You have the following setting options:
Table 4-1
Parameters and their default settings
Parameters
Diagnostics,
Missing supply voltage L+
Diagnostics
Wire break
1
Wire break
check
2
Operating mode
Input delay
3
Hardware interrupts positive
edge
3
Hardware interrupts nega‐
tive edge
3
Potential group
The wire break diagnostics can only be enabled when the "Check for wire break" parameter is enabled.
1
If you use simple encoder contacts, you need to connect a resistor in parallel to enable a wire break check to be performed
2
when the contacts are open. The resistor used depends on the nominal input voltage of the module (see table 2-2).
When time stamping with an accuracy of 1 ms is enabled, the input delay on all channels is switched off and the pulse
3
stretching and hardware interrupt for positive/negative edge is disabled on all channels (not adjustable).
Parameter reassignment
Each configuration change resets the corresponding reaction.
14
Value range
● Enabled
● Disabled
● Enabled
● Disabled
● Enabled
● Disabled
● Enabled
● Disabled
● None
● 0.05 ms
● 0.1 ms
● 0.4 ms
● 0.8 ms
● 1.6 ms
● 3.2 ms
● 12.8 ms
● 20 ms
● Enabled
● Disabled
● Enabled
● Disabled
● Use potential group of the left
module
● Allow new potential group
[ID: 91143428107]
Default
Enabled
Enabled
Enabled
Enabled
3.2 ms
Disabled
Disabled
Use potential
group of the left
module
Digital input module DI 8x24...125VDC HA (6DL1131-6DF00-0PK0)
Parameter re‐
Efficiency range
assignment in
RUN
Yes
Module
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
No
Module