Siemens SIMATIC TP900 Comfort INOX PCT Compacte gebruiksaanwijzing - Pagina 37
Blader online of download pdf Compacte gebruiksaanwijzing voor {categorie_naam} Siemens SIMATIC TP900 Comfort INOX PCT. Siemens SIMATIC TP900 Comfort INOX PCT 48 pagina's. Hmi devices; comfort panels
Ook voor Siemens SIMATIC TP900 Comfort INOX PCT: Compacte gebruiksaanwijzing (42 pagina's)
Sinusoidal interference
The following table shows the EMC behavior of the modules with respect to sinusoidal
interference. This requires the HMI device to meet the specifications and directives for
electrical installation.
Sinusoidal interference
HF radiation (electromagnetic
fields) according to IEC 61000-4-3
HF current feed on cables and
cable shields according to
IEC 61000-4-6
Emission of radio interference
The following table shows the emitted interference from electromagnetic fields according to
EN 61000-6-4, measured at a distance of 10 m.
From 30 to 230 MHz
From 230 to 1000 MHz
See also
Notes about usage (Page 14)
5.4
Mechanical ambient conditions
5.4.1
Storage conditions
The following information is for a device that is transported and stored in its original
packaging.
The device meets the requirements according to IEC 60721-3-2 Class 2M2 with the following
amendments and limitations:
Type of condition
Free fall
Vibration according to IEC 60068-2-6
Shock according to IEC 60068-2-27
Comfort Panels INOX PCT
Compact Operating Instructions, 05/2018, A5E38804191-AA
Test values
80% amplitude modulation at 1 kHz
to 10 V/m from 80 MHz to 1 GHz
•
to 10 V/m from 1.4 GHz to 2 GHz
•
to 1 V/m from 2 GHz to 2.7 GHz
•
Test voltage 10 V with 80% amplitude modulation at 1 KHz in
the 10 KHz to 80 MHz range
< 40 dB (μV/m) quasi-peak
< 47 dB (μV/m) quasi-peak
Permitted range
≤ 1 m
5 .. 8.4 Hz, deflection 3.5 mm
8.4 ... 500 Hz, acceleration 1 g
250 m/s
Technical specifications
5.4 Mechanical ambient conditions
, 6 ms, 1000 shocks
2
37