Tests
3.3 Cooling system test
3. The values sensed by the sensors are displayed on the test station computer:
4. The measured values from the sensors are compared with the reference values of the
Result
The test is passed if the measured values lie within the tolerances.
● Temperature in the supply line ±5 K
● Conductivity ±0.2 µS/cm
● Temperature in the supply line ≤40 °C
● Conductivity ≤2 µS/cm
3.3.4
Leakage monitoring
Fundamentals
The drive cooling circuit is equipped with a leakage monitoring function. The leakage sensor
function is tested.
Test procedure
1. The cooling system is switched on. The auxiliary voltage is present.
2. Moisture/water is applied to one leakage sensor.
3. A message is displayed on the test station computer.
Result
The test is passed if a message is displayed on the test station computer.
32
– Temperature in the supply line
– Conductivity
cooling unit.
SINAMICS GL150 6SL3855 F03 F70 F76 F79 F98 E11
Reference Manual Rev.201902141423 GL150 wassergekühlt