3.1.1. Nodal block for the monitoring direction MAoSLi
The symbol name encrypts the most important block features as follows:
MAoSLi_MD_pDB
MAoSLi_MD_pDB
MAoSLi_MD_pDB
MAoSLi_MD_pDB
The available MAoSLi-functional blocks are shown in the following overview.
Block
MAoSLi_MD_pDB
Illustration of the necessary interconnection – here exemplifying in a CFC-plan:
SIPLUS RIC IEC on S7 V1.5
Functional description
MAo is the abbreviation for Master block output. It is an output block. The
output of the block is the information contained in the message (in this
case to an image DB)
SLi is the abbreviation for Slave-block input. It is a process acquisition
block. The block captures the information in the image-DB and hands it
over to the IEC-Slave.
MD is the abbreviation for Monitoring Direction. This is the signaling resp.
monitoring direction (subordinated Station SIPLUS RIC IEC on S7
control station)
pDB is the abbreviation for parameterizable by DB (option)
Block.-No.
Function
FB161
Transfer of information in monitoring direction (indications, measured
values etc.) from a subordinated station to the remote station.
Depending on the used SIMATIC CPU the block is applicable for the
transfer of up to 1400 information. The number can be increased by
multiple use of the block