Siemens 125-1957 Gebruikershandleiding - Pagina 36
Blader online of download pdf Gebruikershandleiding voor {categorie_naam} Siemens 125-1957. Siemens 125-1957 48 pagina's. Apogee unit vent controller ⎯ 0 to 10v output
APOGEE Heat Pump Controller—Multi Stage Owner's Manual
Descriptor
Address
AOV1SPAN
31
AOV1START
32
AOV2 SPAN
33
AOV2 START
34
AOV3 SPAN
35
AOV3 START
36
AO DIR.REV
37
AOV1
38
AOV2
39
AOV3
40
DO 1
41
AUX RAD
41
DO 2
42
DO 3
43
HTG 2POS VLV
43
DO 4
44
CLG 2POS VLV
44
26
Application
2281, 2283,
Indicates the width of the voltage range where the actuator,
2284, 2286,
controlled by AO1, moves.
2287
2281, 2283,
Indicates the lower end of the voltage range where the actuator,
2284, 2286,
controlled by AO1, moves.
2287
2281, 2283,
Indicates the width of the voltage range where the actuator,
2284, 2286,
controlled by AO2, moves.
2287
2281, 2283,
Indicates the lower end of the voltage range where the actuator,
2284, 2286,
controlled by AO2, moves.
2287
2281, 2283,
Indicates the width of the voltage range where the actuator,
2284, 2286,
controlled by AO3, moves.
2287
2281, 2283,
Indicates the lower end of the voltage range where the actuator,
2284, 2286,
controlled by AO3, moves.
2287
2281, 2283,
Masking point used to determine NO/NC status of actuators
2284, 2286,
attached to analog outputs.
2287
2281, 2283,
Displays the voltage signal to AO1.
2284, 2286,
2287, 2299
2281, 2283,
Displays the voltage signal to AO2.
2284, 2286,
2287, 2299
2281, 2283,
Displays the voltage signal to AO3.
2284, 2286,
2287, 2299
2287, 2299
Digital output 1 controls a 24 Vac load with an ON or OFF
status.
2281, 2283,
The actual status of auxiliary radiation two-position actuator.
2284, 2286
2281, 2283,
Digital output 2 controls a 24 Vac load with an ON or OFF
2284, 2286,
status.
2287, 2299
2287, 2299
Digital output 3 controls a 24 Vac load with an ON or OFF
status.
2281, 2283,
The actual status of the two -position heating valve.
2284, 2286
2299
Digital output 4 controls a 24 Vac load with an ON or OFF
status.
2281, 2283
The actual status of the two -position cooling valve.
Description
Siemens Building Technologies, Inc.