4.1

Operating access levels

Building Technologies
Fire Safety
XC10xx-A operation is organized in several operating access levels.
Operating access level 1
This level gives access to:
-
silence buzzer
-
led test
-
fault detailed display
-
alarm counter display (XC1003-A and XC1005-A only)
Operating access level 2
This operating access level gives access, after code input on keyboard (4 2 3 3 by
default or personalized) or by key (option), to the following controls:
-
silence buzzer
-
silence / re-sound sounders
-
automatic blocked / automatic and manual blocked
-
disable / enable
-
test of zones 1...4
-
reset
-
test of sounders, warning panels, RT-alarm and RT-fault
Operating access level 2 is automatically disabled after 4 minutes if no handling is
carried out for this period.
To enable operating access level 2, enter the default code « 4 2 3 3 » on the
keypad or insert the key into the lock and turn it 90° clockwise (to the right):
LED « Operating access » (10) lights up (fixed)
In order to again block operating access Level 2, turn the key to the starting
position and remove it from the lock:
LED « Operating access » (10) is no longer lit
-
Operating access level 2 is automatically disabled after 4 minutes if no
handling is carried out for this period.
-
Operating access level 2 can be turned back manually to level 1 by entering
the same code (default: 4 2 3 2), without having to wait 4 minutes
In normal operation, only the green LED « System on » (1) is lit up and only
operating access level 1 operations can be carried out. However, note that:
-
yellow LED « Manual blocked » (14) or « Automatic blocked » (16) or both can
be lit up (fixed)
-
yellow LED « Extinguishing blocked » (11) can be lit up (fixed)