Siemens 15-FSV-500 Installatie, bediening en onderhoud - Pagina 27

Blader online of download pdf Installatie, bediening en onderhoud voor {categorie_naam} Siemens 15-FSV-500. Siemens 15-FSV-500 48 pagina's. Vacuum circuit breakers fsv series and msv series

Siemens 15-FSV-500 Installatie, bediening en onderhoud
Interrupter/Operator
Description

Capacitor Trip Device

The capacitor trip device is an a u x i l i ary t r i p p i n g option p rovid­
ing a short term means of sto ring adeq u ate electrical energy
to ensure breaker t r i p p i n g .
T h i s device i s a p p l i e d i n breaker i n stallations lacking i n depen­
dent auxili ary control power o r statio n battery. In such i n stal­
lations, control power i s usually de rived from the primary source.
I n the event of a pri mary sou rce fault, o r d i stu rbance with at-
tendant depression of the primary source voltag e , the capac­
itor trip device will provide short term tripping energy for breaker
ope n i n g due to relay operation.
The capacitor t r i p converts
120
a
fu l l wave voltage which i s used to charge a large capac­
DC
itor to the peak of the converted wave, see below.
Page
22
or
control voltage to
240 VAC