3 Mode of Operation

Mode of Operation
3
3.1

General overview

Figure 3-1
of the TIA Portal project.
Figure 3-1
MAIN
[OB 1]
ReadWrite
The core functionality includes the function block "EbmPapst".
This block is called in the cyclic organization block "Main".
The interfaces of FB "EbmPapst" are fed from the data blocks
"Register" (this DB contains the register structure and the order of the data to
be read) and
"Tags" (this DB contains the tags to parameterize and operator the FB
"EbmPapst").
The following system blocks are called in the FB "EbmPapst":
"Modbus_Comm_Load" [FB640] to initialize the Modbus RTU communication
"Modbus_Master" [FB641] for data exchange of the S7-1200 as the master
with the ebm-papst fans as the slave
Controlling several fans (ebm-papst) via Modbus RTU
Entry ID: 109476801,
V2.0,
shows the chronological sequence of the block calls in the control part
EbmPapst
LGF_
Impulse
User program
09/2018
Send_
Config
[FB611]
Modbus_
Comm_Load
[FB640]
Receive_
Config
[FB612]
Send_P2P
[FB613]
Modbus_
Receive_
Master
P2P
[FB641]
[FB614]
Receive_
Reset
[FB617]
SERIALIZE
[FC890]
System blocks
Register
Tags
Data
blocks