TERMINAL BLOCK
F
N
230~V ±10%
(*) In order to use the floating control the only possible
connection is between terminal M and Y1/Y2. Do not connect
Y1/Y2 to phase (F) F) or neutral (N)
Label
Description
Function
F
230Vac
Power Supply
N
Y
0..10Vdc
Modulating
Control Input
0V (Com-
M
mon)
Y1
Open
Floating Con-
trol Input
Y2
Close
V+
16 Vdc
Voltage
Output (max
0V (Com-
25mA)
M
mon)
U
2÷10Vdc
Feedback
Output Signal
0V (Com-
M
mon)
Note: To avoid damages to electronic components caused by the
PCB bending, do not press too much while fixing the terminal
block.
GROUND CONNECTIONS
Connect the ground terminal to the proper screw labelled with the
ground symbol as shown in the picture here below.
U
Y
M Y1 Y2
*
Max wire
Wire Size
Length
AWG16
(min 1mm
-
75m
2
max 1.5mm
)
2
AWG20
(min 0.5mm
-
200m
2
max 1.5mm
)
2
AWG20
(min 0.5mm
-
200m
2
max 1.5mm
)
2
AWG20
(min 0.5mm
-
200m
2
max 1.5mm
)
2
AWG20
(min 0.5mm
-
200m
2
max 1.5mm
)
2
ground terminal
SAFETY PRESCRIPTIONS
230 V products
Install on the power supply line a protecting device to avoid
•
short circuits (fuse or magneto-thermic) according to the spec-
ifications in force;
•
in case of accidental removal of the cover to make sure that
power is disconnected before working on the actuator or near it;
•
the products are maintenance free.
WIRING DIAGRAMS
3-point Floating Control
230Vac
Controller
Neutral
Modulating Control (o-10 Vcc)
230Vac
Controller
Command +
Command -
Neutral
MVE
Open
Y1 F
Close
Y2
M
N
MVE
F
Y
M
N
Page 4