Actulux SVM 24V-5A Gebruikershandleiding en installatie-instructie - Pagina 4
Blader online of download pdf Gebruikershandleiding en installatie-instructie voor {categorie_naam} Actulux SVM 24V-5A. Actulux SVM 24V-5A 11 pagina's. For fire ventilation
- 1. Table of Contents
- 2. General Description
- 3. Safety Rules During Installation and Operation
- 4. Explosion Danger
- 5. Installation
- 6. Yearly Legal Requirement of Maintenance and Control
- 7. Connection to Motor- (Actuator) Outputs and Line Monitoring
- 8. Current Limiter Type LIP
- 9. Connection of Smoke-/Heat Detectors
- 10. Comfort Ventilation - Connection and Settings
- 11. Fuse Specifications
- 12. Connection of Weather Sensor / Close All Function
- 13. Special Functions
- 14. Cable Sizes
- 15. Part Nos. and Accessories
- 16. Technical Specifications
+
Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A
-
+
-
Connection to motor- (actuator-) output and line monitoring
The actuators (motors) must be connected to the actuator output on the output terminals 2-3.
It is possible to connect and disconnect the line monitoring on the actuator output (the factory setting is
"connected"). The cables to the actuators can be connected in series or parallel or a combination of these
(please see drawing with examples or connection diagramme on the central pages).
It is important to keep the right polarity of the cables - The actuators must always be connected through a
current limiter, e.g. the Actulux LIP or similar.
Cable monitoring (line monitoring) on the motor output
The control is equipped with 3 possible settings for cable
monitoring (line monitoring), which can be configured by
means of jumper J2.
Jumper J2 mounted in pos. »Motor line«
Line monitoring between terminal 2-3.
Jumper J3 (actuator output) is set according to
the number of termination resistors (27KΩ) to
be detected – 1 to max. 4 lines can be detected
by moving jumper J3 – this means that the cable
installation between the control panel and the
actuators can be established in series connection
(cable connection from e.g. skylight 1, further
to skylight 2, etc.), or parallel connection (cable
connection from each skylight to the control), or
a combination of these. However, as mentioned
max. 4 different lines can be detected each
terminated with a 27KΩ resistor.
For SVM 24V-5A the max. allowed current is
5A, For SVM 24V-8A it is 8A.
Jumper description
J3
Number of connected 27Kohm terminal
resistors for actuator output
J2
Chooses line monitoring through motor
terminals 2-3 (Mot Mon) or separate
wire terminals 1-3 (Ext Li Mon), or no
line monitoring when J2/J3 is removed
Fuse 8A for actuator output
F1
24V
Red 2,5mm2
Black 2,5mm2
- 24VDC +
M ax. 8A
FUSE F1 - fast
Actuator
M otor line m onitor
Ext 3 wire m onitor (line 1)
J2
4
J3
3
2
1
Max. Torque 0.5 Nm
1
2
PE
L1
N 1
Line 1
Actuator
24V O ut
1 Cannel LIP 7
1
2
Blue
5
1
2
M1
Blue
Blue
5
7
6
Brow n
2
1
M1
M2
Next LIP
6
8
Brown
Brown
3
4
2 channel LIP 6
Next LIP
6
Potmeter for
RESET
comfort features
M ax.
YEL
YEL
YEL
AC FAIL
LINE FAIL
BATT LO W
Jumper J2 in pos. »Ext 3 wire«.
Line monitoring between terminal 1-3:
With jumper J3 (actuator output) it is chosen, how
DIP settings see page 13
NTC
many lines (number of 27KΩ) you wish to detect - the
same way as the motor line.
This setting demands 3 wire cable from motor output
to motor.
BLUE
Jumper J2/J3 is not mounted - No line monitoring
DO M E O PEN
Keyboard
for actuator output.
Without keyboard jumper mounted
Max. Torque 0.5 Nm
Current limiter type LIP function and setting (if mounted)
Alarm Out
Failure Out
The current limiter type LIP (mounted on the opening system) is used as current limiter between the
4
5
6
7
8
9
10
11
12
13
14
15
24V/48V DC supply and 1 or 2 actuators. When the adjusted current limit is reached, the speed of the
3
actuators is reduced. When the max. power on the actuator is exceeded, the actuator stops. On the
24V /48V types (LIP5, LIP6 or LIP7) max. 3 times overload cut outs in the same direction is allowed.
After that it will not be possible to run in this direction again, before the motor has run in the opposite
direction. This in order to protect the actuator gear mechanism.
1
2
3
4
6
7
Please note that when opening, the red LED in the LIP must light. This indicates that polarity to
2,2KΩ
actuator is correct.
10 KΩ
J1
Fire switch BVT No. 1
1
2
3
4
6
7
Table of LIP settings
1
2
3
4
6
7
2,2KΩ
Extra relay print #111655
Opening System
10 KΩ
3A/1,5A SA Power
J1
provides 4 additional
24V/48V
Single, Double, Large
Fire switch type BVT.
potential free switches
Fit J1 in last BVT for
each 30V 0,5A
DIP 1
line m onitoring
ON
DIP 2
OFF
Type
Board
Board
no.
descrip.
LIP5
121315 A043
LIP6 *
121330 A044
LIP7
121305 LIP7
Basic
LIP7
121306 LIP7
TA
LIP7***
121308 LIP7
OC
* SA Power Large - parallel operation: Jumper OPT mounted - both motors stop at the same time if one stops because of overload.
** When DIP4 is OFF = Tandem mode - both motors stop at the same time if no current flows in one. (1.5 sec. reaction time)
*** Requires actuator with Reed. (3-core incl. black cable)
**** OFF = No delay between Master og Slave / ON = Seven sec. delay between Master og Slave.
Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A
M in
→
ON
→
OFF
DIP NO 1
2
3 4
5
6 7
8
9 10
11
12
J15
J9
J4
J5
J6
J7
START TERM .
M ASTER
SLAVE
END TERM .
→
→
Set J11 for batteri backup
→
J11
of terminal 23
16
17
18
19
20
21
22
23
AW R-24
24V
AC/DC
L1 In
L2
No.1
L1 O ut
Down
L1 In
Up
L2
Nr.2-20
L1 O ut
4A/2A SA Power
2.5A/1,25A SA Power
Single, Double, Large
Mini
OFF
ON
(only last sensor)
ON
ON
Voltage and
DIP
DIP
DIP
DIP
DIP
function
1
2
3
4
5
24/48V 1 channel
27K
ON
24/48V 2
OFF ON** 27K ON
channels
24/48V 1 channel
27K
ON
See
24/48V 1 channel
27K
ON =
OFF = Slave
diagram
Tandem
ON
Com
ON = Master
above
24/48V
27K
ON =
OFF = Slave
1 channel Syncro
ON
Com
ON = Master
m/position ind.
7
To start communication
LD3 + LD2 flashes for
5 sec. when flatcable
is connected.
LD1 (power) will
Actuator
illuminate when power is on.
J2
Motor line monitor
If LD2 (fireswitch) illuminates
Ext 3 wire monitor (line 1)
linefault on fireswitch.
If LD3 (fireclose) illuminates
4
J3
3
linefault on fireclose.
2
Firemands Pr
1
1
2
3
Line 1
+
-
External fi
Actuator
24V Out
CLOSE
1
Power
LED 1 Green
Open
LED 2 Red
Close
LED 3 Red
SWM Add-on
+
27K Ohm
(Only last
actuator)
A
H
D
D
DRAWN BY:
#111960
#111961
TITLE:
E
2,5A/1,25A Rotary 100
LIP5/6
2A/1A SA Power Mini
LIP7
OFF
OFF
DIP
DIP
DIP
6
7
8
Not mounted
M1-M2 delay =ON
Not mounted
OFF = Syncro Mode
Not in
ON = Tandem Mode ****
use
OFF = Syncro Mode
Not in
ON = Tandem Mode ****
use