End of installation.
D

12 - HOME AUTOMATION WIRING

It is possible to connect the unit to a Home Automation system, according to the following instructions:
13 - PUMP DOWN (See Installation Instruction of Outdoor Unit)
Pump down means collecting all refrigerant gas in the system back into the outdoor unit without losing gas. Pump down
is used when the unit is to be moved of before servicing the refrigerant circuit.
14
- TEST OF THE SYSTEM AND CONTROL OF THE AIR VOLUME TO THE
OUTLET GRILLES
Below you can find the head curves (static pressure) available at the unit outlet according to the air flow and the speed
selected on the remote control:
60
50
40
30
20
10
0
0
100
SDIAS8DC
3
2
200
300
400
m3/h
ON/OFF (Terminals O O) - DEFAULT FACTORY STATE: CLOSED
Contact open: the unit does not operate (always OFF) - inputs from
the remote control unit are not processed.
Contact closed: the unit operates in the normal way, according to the
inputs coming from the remote control unit.
ALARM (Terminals L N) :
These terminals are connected to the contact (normally open) of a
power relay that is activated every time any alarm occurs on the unit.
When an alarm occurs, the poles of the terminal block will have a
voltage of 220-240V ~ 50Hz Max. electric load: 3A
5
4
8
7
6
500
600
700
12