1. Introduction
The analog - digital - converter AWA/2X12B is used as an input module for the electric camswitches of
the CamCon series. The converter has two independent voltage - (-10V - +10V respective 0 - +10V) or
power inputs (0 - 20mA) with a resolution of 12Bit, that can be connected via a 6 pole datacable to the
external interface of the CamCon devices DC50/561, 90 and 115. By switching several devices in
series connection it is possible to connect up to 5 AWA/2X12B analog digital converters.
2. Assembly
The device is clip-locked onto an "EN carrier rail" in the switchboard (see also chapter
"6.3. Calibration" on page 8). The grounding pins and cable mantlings are to be put on the
shortest way possible onto serial grounding clip next to the device. The grounded
assembly plate and its electrical connection to the "EN carrier rail" allow an excelent
grounding of the disturbances onto the covering. All cable connections are to be switched
in a cold state ! The external interface of the CamCon (e.g. DC16/50/90 or DC115) is
connected with a cable of the type: KKyy/IO-XX (yy = CamCon Type / XX = length in
meters) to the plug "external interface IN" or "ext.Int. IN" on the module. Every other
device is connected to the plug "external interface OUT" or "ext.Int. OUT" with a cable
of the same type. The data lines of the external interface have to be galvanically
separated with an optical coupler, they have to be placed and covered separately and the
cover has to be grounded on both ends. Analog signals have to be placed and covered
separately and the cover has to be grounded on one end. The supply voltage has to be
connected separatly for every module and measures 24V DC +/-20%.
Note:
The analog - digital - converter has to be switched to the end of the interface row.
3. Status LED
The analog - digital - converter has 2 status LEDs (see also chapter 6.3. Calibration).
LED 1
indicates the presence of supply-power.
LED 2
indicates that no data exchange via a CamCon DC50, 90 or DC115CamCon is done.
Possible causes are: The cable length adjusted at the CamCon outruns the maximum length
of 300 meters, the CamCon DC50, 90 or DC115 is switched off, i.e. the data exchange is
interrupted (broken wire).
Edition: Jun. 17
Analog - Digital - Converter
AWA/2X12B
example