Fuse and Alarm Panel Wiring
Figure 24
Field
BITS
LAN
ENVIR
ALARMS
IN
Unpacking and Installing the Cisco ONS 15454 Four-Shelf and Zero-Shelf Bay Assembly
26
Wire-wrap pin layout in a Release 3.4 ANSI shelf assembly
A
B
A
B
A
B
1
1
1
1
2
2
2
2
3
3
3
3
4
4
4
4
BITS
LAN
IN
FG1
FG2
FG3
FG4
Pin
Function
A1
BITS Output 2 negative (–)
B1
BITS Output 2 positive (+)
A2
BITS Input 2 negative (–)
B2
BITS Input 2 positive (+)
A3
BITS Output 1 negative (–)
B3
BITS Output 1 positive (+)
A4
BITS Input 1 negative (–)
B4
BITS Input 1 positive (+)
Connecting to a hub, or switch
RJ-45 pin 6 RX–
A1
B1
RJ-45 pin 3 RX+
A2
RJ-45 pin 2 TX–
B2
RJ-45 pin 1 TX+
Connecting to a PC/Workstation or router
A1
RJ-45 pin 2 RX–
B1
RJ-45 pin 1 RX+
A2
RJ-45 pin 6 TX–
B2
RJ-45 pin 3 TX+
A1
Alarm input pair number 1: Reports
closure on connected wires.
B1
A2
Alarm input pair number 2: Reports
closure on connected wires.
B2
A3
Alarm input pair number 3: Reports
closure on connected wires.
B3
A4
Alarm input pair number 4: Reports
closure on connected wires.
B4
A5
Alarm input pair number 5: Reports
closure on connected wires.
B5
A6
Alarm input pair number 6: Reports
closure on connected wires.
B6
A7
Alarm input pair number 7: Reports
closure on connected wires.
B7
A8
Alarm input pair number 8: Reports
closure on connected wires.
B8
A9
Alarm input pair number 9: Reports
closure on connected wires.
B9
A10
Alarm input pair number 10: Reports
closure on connected wires.
B10
A11
Alarm input pair number 11: Reports
closure on connected wires.
B11
A12
Alarm input pair number 12: Reports
closure on connected wires.
B12
A
B
A
B
A
B
7
1
ACO
8
2
5
9
3
6
10
4
ENVIRONMENTAL ALARMS
IN/OUT
IN
IN
FG5
FG6
FG7
Field
Pin
A1/A13 Normally open output pair number 1
ENVIR
ALARMS
B1/B13
IN/OUT
A2/A14 Normally open output pair number 2
B2/B14
N/O
A3/A15 Normally open output pair number 3
B3/B15
A4/A16 Normally open output pair number 4
B4/B16
ACO
A1
Normally open ACO pair
B1
CRAFT
A1
Receive (PC pin #2)
A2
Transmit (PC pin #3)
A3
Ground (PC pin #5)
A4
DTR (PC pin #4)
A1
Alarm output pair number 1: Remote
LOCAL
audible alarm.
ALARMS
B1
AUD
A2
Alarm output pair number 2: Critical
(Audible)
audible alarm.
B2
N/O
A3
Alarm output pair number 3: Major
audible alarm.
B3
A4
Alarm output pair number 4: Minor
audible alarm.
B4
A1
Alarm output pair number 1: Remote
LOCAL
visual alarm.
ALARMS
B1
VIS
A2
Alarm output pair number 2: Critical
(Visual)
visual alarm.
B2
N/O
A3
Alarm output pair number 3: Major
visual alarm.
B3
A4
Alarm output pair number 4: Minor
visual alarm.
B4
A
B
A
A
B
A
1
1
1
2
2
2
3
3
3
4
4
4
MODEM
CRAFT
LOCAL ALARMS
VIS
AUD
FG8
FG9
FG10
Function
If you are using an
AIC-I card, contacts
provisioned as OUT
are 1-4. Contacts
provisioned as IN
are 13-16.
B
A
B
11
12
IN
FG11
FG12
78-13271-05