Acuity Brands Lighting IS Handmatig - Pagina 5

Blader online of download pdf Handmatig voor {categorie_naam} Acuity Brands Lighting IS. Acuity Brands Lighting IS 18 pagina's.

Installation Instructions
RSX LED
4. The luminaire is supplied with a variety of slots to
align with existing pole mounting drill patterns. The top
hole of the luminaire arm has a key hole slot.
Place the luminaire onto the top bolt by passing the
head through the key slot and resting the luminaire
down securely in place (See Fig 3).
WARNING: THE LUMINAIRE IS NOT COMPLETELY
LOCKED DOWN YET. SPECIAL CARE MUST BE TAKEN TO
AVOID JARRING THE LUMINAIRE FROM ITS RESTING
POINT
Ensure the luminaire is resting securely on the top bolt
and snug the bolt but do not completely tighten yet.
Thread the second bolt through the arm slot and into
the available threaded hole of the mounting bar (See
Fig 4).
5. The luminaire is supplied with a clearance slot in the
back to allow wires to be pulled into the pole on exist-
ing hole patterns. Insert the wires through the clear-
ance slot shown in Figure 5 and pull them into the pole.
6. Ensure luminaire is straight/level making sure that
no wires are pinched, tighten the two bolts with a 3/8
socket to 20-30ft-lbs (overtightening can damage com-
ponents and void warranties). Make sure that wires are
not pinched and tuck excess wire up into the luminaire
mounting area.
7. Reinstall the cover removed in step 1, tighten the two
captive screws with the 9/64 Allen wrench to 18-20 in-
lbs (overtightening can cause thread stripping and void
all warranties) (See Fig 6).
8. Make wire connections in the pole, observing proper
voltage and polarity. Connect green ground wire from
the fixture to the field ground wire. Secure wires; push
back into pole and replace pole cap.
©2016 Acuity Brands Lighting, Inc.
All Rights Reserved.
Lithonia Lighting Outdoor
One Lithonia Way, Conyers, GA 30012
Phone: 800-279-8041 Fax: 770-918-1209
www.lithonia.com
Part Number: IM-459 Rev A
Revision Date: 8/29/19
Page #3