ABB Relion 615 series Snelstarthandleiding - Pagina 2

Blader online of download pdf Snelstarthandleiding voor {categorie_naam} ABB Relion 615 series. ABB Relion 615 series 4 pagina's. Motor protection and control
Ook voor ABB Relion 615 series: Snelle installatiehandleiding (20 pagina's), Snelle installatiehandleiding (16 pagina's), Snelle installatiehandleiding (20 pagina's), Snelle installatiehandleiding (16 pagina's), Engineering Handleiding (20 pagina's), Handleiding voor toepassingen (20 pagina's)

ABB Relion 615 series Snelstarthandleiding
2
Q U I C K S TA R T G U I D E R E L I O N ® 6 1 5 S E R I E S
Using the local HMI
Accessing main menu and changing parameters
Press
to navigate between main menu, measurements
and single-line diagram.
Press
and select which setting value you want to change
and press
to change it with
mark at the same line with parameter value, you have to first
select which setting group parameter you want to change.
If there is no "#" mark then you can change the value directly
by pressing
and then with
You can change all parameters in the same way. The most
common function block names are described at the end of
this document.
Storing settings
After making changes to parameters they have to be stored
to get them into use. Store the settings by going back to main
menu by pressing
or using the
confirmation to commit changes, answer "Yes". Some changes
require the IED to reboot before the changes can be taken into
use. Reboot the IED by going to
General → Software reset
or switching the auxiliary power
off and back on.
Changing the overcurrent start value
Menu → Settings → Settings →
default 1
→ Current Protection → PHLPTOC1 →
and press
Start value
Changing function block naming from IEC 61850 names
to IEC 60617 or ANSI
Menu → Configuration → HMI → FB Naming convention
Checking binary input value
Menu → Monitoring → I/O Status → Binary input values →
select correct BIO card
Checking fault records and the currents and voltages
of the latest faults
Menu → Monitoring → Recorded data → Fault record
Changing the display contrast
Hold
and press
or
If you want to store the contrast go first in the menu and then
go back to the default view, so that A (Administrator) appears
to the right upper corner. If authentication is enabled you need
to login and then change the contrast.
or
keys. If there is "#"
or
or
or
keys.
key. When IED asks
Menu → Configuration →
setting group,
select
to change the display contrast.
Clearing events and indications
There are two ways to do this:
• Go to clear menu by pressing
the main menu. Then select what you want to clear and
press
→ press
(Clear text will appear and Cancel will
disappear) and then press
• Press
hold for three seconds to clear indications and
immediately after that three seconds again to clear LEDs.
Checking IED order code, serial number, HW revision
and software version
Menu → Information → Product Identifiers
Display header area
The icon area at the upper right corner of the dislay shows
the current action or user level. These are described below:
S = Parameters are being stored, ! = Warning and/or indication
V = Viewer, O = Operator, E = Engineer, A = Administrator
I/O status
Menu → Monitoring → I/O status
From here you can check the input and output data of
a function block. More information about function block
operation can be found under
output statuses, communication monitoring etc are also
available.
Changing the language
Menu → Language
Or you can push
and
will be changed. English is always the default language and
there can be maximum of two additional languages in the IED.
Changing the default view
Menu → Configuration → HMI → Default View
Reading the Internal Relay Fault (IRF) code
Menu → Monitoring → IED Status → Self-supervision
Restoring factory settings
Warning! All parameter settings will be overwritten with the
default values. During normal use, a sudden change of the
settings can cause a protection function to trip.
Menu → Configuration → General → Factory Setting
Using the local HMI
Complete customer documentation is available in the product
pages that can be accessed through abb.com/relion.
or selecting
Clear
from
.
Monitored
data. Physical input/
anywhere in the menu and language