INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS

Batteries
5
3
Filter
Flat head
7
wood screw
2
Wireless remote control

Optional Installation Parts

Part
Parts name
code
Refrigerant piping
Liquid side : Ø6.35 mm
Gas side
: Ø9.52 mm
(RAS-B07, 10, 13G3KVSG-E)
A
(RAS-B07, 10, 13G3KVSGB-E)
: Ø12.70 mm
(RAS-B16G3KVSG-E)
(RAS-B16G3KVSGB-E)
Pipe insulating material
(polyethylene foam, 6 mm thick)
For RAS-B07, 10, 13G3KVSG-E
B
RAS-B07, 10, 13G3KVSGB-E
(polyethylene foam, 8 mm thick)
For RAS-B16G3KVSG-E
RAS-B16G3KVSGB-E
C
Putty, PVC tapes
Refrigerant piping
must be protected from
physical damage.
Install a plastic cover or
equivalent.
Vinyl tape
Apply after carrying
out a drainage test.
Remote control
4
holder
Q'ty
One
each
1
One
each
Hook
1
Installation
plate
Shield pipe
Saddle
Extension drain hose
(Not available, provided
by installer)
Fixing bolt arrangement of outdoor unit
Secure the outdoor unit with fi xing bolts and nuts if the unit is likely to be
exposed to a strong wind.
Use Ø8 mm or Ø10 mm anchor bolts and nuts.
If it is necessary to drain the defrost water, attach drain nipple " and cap
water proof # to the bottom plate of the outdoor unit before installing it.
108 mm
28 mm
When using a multi-system outdoor unit, refer to the installation manual
provided with the model concerned.
6
For the rear left, bottom left and left piping
Wall
Cut out a piece of SPACER from indoor
unit packaging box, roll it and insert
between the indoor unit and wall to tilt
the indoor unit for better operation.
The auxiliary piping can be connected to
the left, rear left, rear right, right, bottom
right or bottom left.
Right
Rear
right
Bottom
Rear
right
left
Bottom left
Do not allow the drain hose to get slack.
Cut the piping
hole sloped
slightly.
Make sure to run the drain hose sloped
downward.
Insulate the refrigerant pipes separately
with insulation, not together.
6 mm or 8 mm thick heat
resisting polyethylene foam
125 mm
Air inlet
Air outlet
90 mm
600 mm
Drain outlet
Left