Setting
0 - 100
Parameter 8: Percentage change in wattage (Whole HEM)
Percentage change in wattage to induce a automatic report
Size: 1 Byte, Default Value: 10
Setting
Parameter 9: Percentage change in wattage (Clamp 1)
Percentage change in wattage to induce a automatic report
Size: 1 Byte, Default Value: 10
Setting
0 - 100
Parameter 10: Percentage change in wattage (Clamp 2)
Percentage change in wattage to induce a automatic report
Size: 1 Byte, Default Value: 10
Setting
0 - 100
Parameter 11: Percentage change in wattage (Clamp 3)
Percentage change in wattage to induce a automatic report
Size: 1 Byte, Default Value: 10
Setting
0 - 100
Parameter 13: Enable /disable reporting
Enable /disable reporting CRC-16 Encapsulation Command
Size: 1 Byte, Default Value: 0
Setting
0
1
Parameter 100: Reset parameter 101-103
Size: 1 Byte, Default Value: 0
Setting
1
Parameter 101: Setting automatic report flags Group 1
Example:   1 + 1024 = Value 1025 If you want to report everthing, you would add the whole table together and set in to 101.
Please, see table in usage.
Size: 4 Byte, Default Value: 0
Setting
1
2
4
8
Parameter 102: Setting automatic report flags Group 2
Example: 1 + 1024
Value 1025 If you want to report everthing you would add the whole table together and set in to 102
Description
Valid value
Description
Description
Valid value
Description
Valid value
Description
Valid value
Description
disable
enable
Description
reset parameter 101-103
Description
Report Total HEM - KWH
Report Total HEM - Watt
Report Total HEM - Voltage
Report Total HEM - Current