Whirlpool WED7500VW Specificaties - Pagina 5
Blader online of download pdf Specificaties voor {categorie_naam} Whirlpool WED7500VW. Whirlpool WED7500VW 8 pagina's. Compact electric dryer with 11 cycles
Ook voor Whirlpool WED7500VW: Gebruiks- en onderhoudshandleiding (20 pagina's), Gebruiks- en onderhoudshandleiding (20 pagina's), Afmetingen en installatie-informatie (1 pagina's), Gebruiksaanwijzing (8 pagina's), Installatie-instructies (2 pagina's)
Venting Requirements
Venting systems for Whirlpool dryers must meet the following
requirements:
■
The capacity to handle 200 CFM of air for each dryer in the
system.
■
A back pressure of -1.0" (-25 mm) water column to
0.6" (15 mm) of water column when measured at the
connection to the dryer.
■
The minimum duct air velocity during normal operating
conditions should be at least 1,100 FPM to keep lint moving
in the air stream. (In a 4" diameter pipe, this requires at
least 96 CFM.)
Back pressure should be measured with an empty dryer, a clean
lint screen and with the dryer operating in the Air Only cycle
(no heat). Use an inclined manometer, such as Dryer model
102 (0"-2" [0 mm - 51 mm] range) or Dryer model 172
(0"-1" [0 mm - 25 mm] range) to measure the back pressure.
See the following illustration.
B
A
A. Dryer - empty and running on Air Only cycle
B. 12" (305 mm) min. of straight pipe - measure
back pressure from the center
C. To vent system
D. 0.6" (15 mm) water maximum back pressure
E. Inclined manometer
Single Dryer Venting Systems
Single dryer venting systems are defined as systems that have
only one dryer unit attached to a residential-type 4" (102 mm)
diameter rigid metal vent system. For single dryer venting
systems, see the Installation Instructions that came with your
dryer to determine the allowable length and number of elbows for
the venting system.
Additional Elbows
In cases in which the Installation Instructions do not address the
vent length for the specific number of elbows required for a
particular application, the following calculations may be used.
(The total vent system length includes all straight and curved
portions of the vent system.):
■
For 90° elbows, reduce the allowable vent system length by
10 ft (3.05 m).
■
For 45° elbows, reduce the allowable vent system length by
6 ft (1.83 m).
For example, if the Installation Instructions state that a dryer is
allowed 40 ft (12.2 m) of total vent length with two 90° bends, and
the installation requires three 90° bends, the total allowable vent
length would be reduced by 10 ft (3.0 m) (from 40 ft [12.2 m] to
30 ft [9.1 m]).
C
D
E
Dryer Airflow
The airflow of a dryer depends on the design of the exhaust vent.
Each dryer model has a maximum rated vent length, shown in the
product literature that is supplied with each model, or on the
Whirlpool.com website. The exhaust airflow of any Whirlpool
produced dryer at the maximum rated vent length is at least
100 CFM. The maximum airflow is 200 CFM. This includes
standard vent and long vent dryer models.
Codes Agency Approvals
All Whirlpool electric dryer models, including "long vent dryers,"
that are sold in the United States and Canada are UL listed
(reference UL2158 standard), and all Whirlpool gas dryer models
are CSA listed (reference ANSI Z21.5.1 standard). These
standards require testing at the maximum-rated exhaust vent
conditions that are published in the product literature for each
individual model. The designation for the UL or CSA listing can be
found on or adjacent to the serial label on the product.
Dryer Closet Installations
Closets used for dryer installation must provide multiple openings
to allow air to flow through the dryer and around the dryer to
dissipate heat. Refer to the product literature for details of room
venting requirements. Any dryer enclosure or room that does not
have an inlet and outlet for an operating forced air HVAC system is
considered a closet, and requires room venting as stated in the
product literature. The room venting can be installed into the walls
of the dryer enclosure, as well as the door, provided it will not be
blocked after the dryer is installed. Refer to the product literature
for minimum clearances between the product and the enclosure
surfaces.
"AF" Code
Certain electronic dryer models have airflow detection
capabilities. (See specific model product literature for details). If
the airflow in the dryer is extremely low, an "AF" code will be
displayed on the control panel. For single dryer venting systems,
this code means that you may have a blocked or partially blocked
vent or that your overall vent system length is too long. To resolve
this issue:
■
Check to see if the vent run from the dryer to the wall is
crushed. Refer to the "Venting Requirements" section of
the Use and Care Guide for more information.
■
Confirm that the vent run from the dryer to the wall is free
of lint and debris.
■
Confirm that the exterior vent exhaust hood is free of lint
and debris.
■
Confirm that your vent system falls within the
recommended run length and number of elbows for the
type of vent you are using. Refer to the "Plan Vent
System" section of the Use and Care Guide for details.
■
Select a Timed Dry heated cycle, and restart the dryer.
■
If the message persists, have your entire home venting run
cleaned.
For multi-dryer venting systems, the "AF" code means that your
vent may be blocked or partially blocked or that the venting
system is creating back pressure in excess of the maximum
allowable 0.6" (15 mm) water column. In this case, the engineering
firm that designed the system should be consulted.
Multiple Dryer Venting Systems
Multiple dryer venting systems must be designed specifically for
each application.
NOTE: It is recommended that an architectural or HVAC
engineering firm be consulted for designing the dryer venting
system.
Connecting a number of dryers to a single vent system is
common in coin-laundry stores and in many apartment buildings.
Listed here are some requirements for examples of three different
multiple dryer venting systems.
5