FirePro FP-08450 Gebruikershandleiding - Pagina 18
Blader online of download pdf Gebruikershandleiding voor {categorie_naam} FirePro FP-08450. FirePro FP-08450 20 pagina's. Fire detection and activation system
Specifications
11
General
Power Supply Input
Detection Output
Circuit 1 Alarm &
Circuit 2 Alarm
Discharge Output
Siren/Strobe Output
Agent Released Input
Dimensions
Material
Ingress Protection
Operating Temperature
Fault Monitoring – External
Fault Monitoring – Internal
Mains Operating Voltage
Mains Operating Current
Backup Power
No. of Detection Zones
Operating Voltage
Detection End-of-line
Maximum Detectors per Zone
Alarm Threshold
Compatible Detectors
Discharge Output Current
Discharge End-of-line
Maximum FirePro Generators
Standard Discharge Delay
Siren/Strobe Output Current
Siren/Strobe Output Protection
Siren/Strobe End-of-line
Maximum Siren/Strobes
Compatible Siren/Strobes
Input Type
Operation
143L x 84W x 31D mm
ABS plastics, black colour
IP54
-40 to 85 degrees Celsius
Circuit 1 Alarm – Open/Closed
-
Circuit 2 Alarm – Open/Closed
-
Siren/Strobe – Open/Closed
-
Discharge – Open/Closed
-
Poly-switch fuse operated
-
Loss of internal 5V supply
-
Internal microprocessor malfunction
-
12-30VDC
20mA on 12V
See FP-08870 / 08871 / 08872 manual
2
12-30VDC (same as main supply voltage)
4k7Ω Resistor
30 Conventional Detectors
-
100m Linear Heat Detection
-
30 Manual Call Points
-
3.6V Fault sensing threshold: 0.53V
Hochiki SLV-AS Smoke Detector
Hochiki DCD-AE3M Thermal Detector
14053 External Call Point
09510 180˚C Linear Heat Detection
2A at 12VDC
3K3Ω Resistor
2 in series at 12VDC
5 seconds from automatic/manual activation
Max 0.5A
0.5A poly-switch resettable fuse
1N4004 Diode
5
Flashni Xenon Sounder Beacon
Thermal Switch, NC, Latching, Non-resettable
Thermal Event >80˚C
23mA on 24V
4A at 24VDC
4 in series at 24VDC
Page | 18