Whirlpool UXD8630DYS0 Gebruiks- en onderhoudshandleiding - Pagina 4

Blader online of download pdf Gebruiks- en onderhoudshandleiding voor {categorie_naam} Whirlpool UXD8630DYS0. Whirlpool UXD8630DYS0 36 pagina's. 30" and 36" retractable (pop-up) downdraft vent system

INSTALLATION REQUIREMENTS
Gather the required tools and parts before starting installation.
Read and follow the instructions
provided with any tools listed
here.
Tools Needed
Jigsaw or keyhole saw
Drill
1/8"(3 mm) drill bit for pilot holes
Pencil
Tape measure or ruler
Flat-blade screwdriver
Phillips screwdriver
3/8"(9.5 mm) nut driver
Level
Pliers
Metal snips
Wire stripper or utility knife
Caulking gun and weatherproof
caulking compound
Parts Supplied
Top trim--stainless
End caps (2)
Lower support legs (2)
Undercounter
mounting brackets (2)
4 x 8 mm screws (16)
3.5 x 9.5 mm screws (3)
31/4 '' x 10" (8.3 x 25.4 cm) rectangular damper
43/4 '' (12.0 cm) motor box
1_,,(6.4 mm) deep cover
Flat vent cover plate
6" (15.2 cm) diameter vent transition with damper
Parts Needed
UL listed or CSA approved 1/2"(12.7 mm) conduit connector
Wall or roof cap with damper to match vent system
Vent system
Home power supply cable
UL listed wire connectors
(3)
Vent clamps/duct
tape as required
s}c@ on
NOTE: Downdraft vent is installed directly behind the cooktop.
Install the downdraft vent first, then install the cooktop.
IMPORTANT:
Observe all governing codes and ordinances.
Have a qualified technician install the downdraft vent. It is the
installer's responsibility to comply with installation clearances
specified on the model/serial rating plate. The model/serial
rating plate is located on the front of the downdraft
vent
above the terminal box cover.
Downdraft vent location should be away from strong draft
areas, such as windows, doors, and strong heating vents or
fans.
Cabinet opening dimensions that are shown must be used.
Given dimensions
provide minimum clearance.
Consult the cooktop manufacturer
installation instructions
before making any cutouts.
Check that the downdraft vent and cooktop location will
clear the cabinet walls, backsplash, and rear wall studs
inside the cabinet.
Check for the minimum distance between the front edge
of the countertop and the front edge of the cooktop. The
minimum horizontal distance between the overhead
cabinets is the same as the width of the installed
downdraft vent.
All openings in ceiling and wall where the downdraft vent will
be installed must be sealed.
Grounded electrical outlet is required. See "Electrical
Requirements"
section.
When installing the downdraft vent, the cabinet drawer will
need to be removed and the drawer front installed
permanently to the cabinet.
Cabinet Construction:
Downdraft vent is designed for use in a cabinet with a depth of
24" (61 cm). Some installations require a countertop deeper than
25" (63.5 cm). See the "Countertop
Cutout Dimensions Chart."
The maximum depth of the overhead cabinet is 13" (33 cm).
Overhead cabinets installed at either side of the downdraft vent
must be 18" (45.7 cm) above the cooking surface.
For Mobile Home Installations
The installation of this downdraft vent must conform to
the Manufactured
Home Construction
Safety Standards,
Title 24 CFR, Part 328 (formerly the Federal Standard for
Mobile Home Construction
and Safety, title 24, HUD, Part 280)
or when such standard is not applicable, the standard for
Manufactured
Home Installation 1982 (Manufactured
Home
Sites, Communities
and Setups) ANSI A225.1/NFPA 501A, or
latest edition, or with local codes.