The 435 BACnet Gateway has been specifically designed to expose the 'router', 'group' and 'device'
parameters from Helvar routers in a designated workgroup through the TCP/IP network. The
BACnet/IP BMS can use this information to control and monitor the lighting, energy and
environmental conditions.
The unit is designed and manufactured to comply with CE Class A, FCC Class A, WEEE (Waste
Electrical and Electronic Equipment), RoHS (Restriction of Hazardous Substances) regulations
and the identification of a substance as Substance of Very High Concern (REACH).
It also complies with the requirements defined in the Council of the European Union Directive on
the Approximation of the Laws of the Member States relating to Electromagnetic Compatibility
(89/336/EEC). For the evaluation regarding the electromagnetic compatibility, refer to the
Declaration of Conformity certificate (available on request).
1.1.

Device limits and compatibility

The 435 BACnet Gateway has the following limitations and compatibility requirements:
Limits:
o
o
o
o
Compatibility:
o
o
o
1.2.

Description of the unit

The 435 BACnet Gateway includes internal HTML configuration pages designed to simplify the
engineering and setting of the interface. These pages make it easier to configure the
communication requirements. The connected Helvar routers appear as a single BACnet device in
the BACnet/IP BeMS, whereas the predetermined parameters appear as predetermined BACnet
object types.
2
Helvar | Data is subject to change without notice.
Single workgroup
Max. 2 units per workgroup (may require different device instance numbers: see the
Guide
).
Max. 300 groups
Max. 2000 BACnet/IP points (overall limit)
Router firmware version 5.2 or above.
Router IP addresses need to have the same first and second octets, i.e. '10.254.x.x'.
Web browsers: Firefox (recommended), Chrome and Internet Explorer.
User