PANEL COMMISSIONING

The system should be commissioned in accordance with the requirements of BS5839 Pt1 as follows:-
1
The complete installation should be checked to ensure that all the cables have been correctly installed
in accordance with the IEE regulations.
2
All the cables must be insulation tested with high voltage test sets prior to the sounders and bases /
detectors being connected.
3
The earth to the panel must be tested.
4
All detectors and sounders must be correctly wired, no spurs, and correctly fitted to the bases.
5
End of line components / resistors (of the correct value) must be fitted to the end of each circuit.
6
Connect the battery and switch on the mains supply.
7
If the panel/system requires set up changes from the default, use Level 3 option – see below.
8
Test the panel as described in the USER GUIDE
9
Test every detector, call point and sounder on the system.
10 Enter the zone text on the front panel main card by removing the slide in zone card. This can be hand
written or via typed via a PC using a free file provided via email.
11 HAND-OVER TO THE USER - as follows:-
a) Teach the user how to operate the panel and test the system, using the USER GUIDE
b) Issue drawings of the wiring.
LEVEL 3 – PANEL SETUP -
The fire panel is factory set as follows:
- All zones set as Latching
- Monitor Input, OFF
- Alarm Delay, OFF
The above settings can be altered to suit various installation requirements.
A Level 3 card has been provided to help the set up process. Open the panel front and change slide in cards
to the level 3 side, see below–w
Fit the small link across pins marked MEM at the bottom centre of the main pcb – close the door and enter
code 4554. Only one function is indicated (flashing led) at any time, all functions must be set up in
sequence. To go straight to a specific setting, press 1 – function until you reach the required setting. After
set up is complete press 4- SAVE CHANGES, remove the MEM link and then press 5 – EXIT.
NOTE, to exit and NOT save the changes - remove the link and then press 5 – EXIT
Panel Front Layout with
Level 3 Set up Card
9
c) Issue a commissioning certificate
hen finished remove and replace cards with main card side showing.
- All zones set as 470R fire type
- Class Change illuminates Fire led, OFF