CALECTRO CALAIR-PR-230V Installatie-instructie - Pagina 12
Blader online of download pdf Installatie-instructie voor {categorie_naam} CALECTRO CALAIR-PR-230V. CALECTRO CALAIR-PR-230V 12 pagina's.
25
Alarm delay
26
DI1 setpoint
27
DI2 setpoint
28
DI1 function
29
DI2 function
30
Override DAC from
MODBUS
31
Override DAC value
32
Override relay from
MODBUS
33
Override relay value
34
Calibration value
35-44
FIFO Alarm log
(*1) Value is multiplied with 10.
(*2) Operation mode
1.
Regulator mode
2. Pressure sensor -50Pa to +50Pa
3. Pressure sensor 0Pa to 100Pa
4.
Pressure sensor 0Pa to 150Pa
5. Pressure sensor 0Pa to 300Pa
6. Pressure sensor 0Pa to 500Pa
7.
Pressure sensor 0Pa to 1000Pa
8. Pressure sensor 0Pa to 1600Pa
9.
Pressure sensor 0Pa to 2000Pa
(*3) Mean operation mode
1.
Regulation on direct pressure value
2. 1.28 sec. mean value
3. 2.56 sec. mean value
(*4) Temperature sensor type
1.
CALAIR-PR-NTC
2. Pt1000
3. Temperature from MODBUS
4.
NONE/OFF
(*5) Digital input operation
1.
Motor alarm function
2. Force setpoint (DI1/DI2 setpoint)
(*6) Register 30 (Override DAC from MODBUS)
must be set to '1'
(*7) FIFO Alarm log (latest alarm on register 44)
0. No alarm
1.
High pressure alarm
2. Low pressure alarm
3. DI1 motor alarm
4.
DI2 motor alarm
5. Temperature sensor error alarm
(*8) Alarm enable
1.
Enable
2. Disable
(*9) Register 32 (Override relay from MODBUS)
must be set to '1'
Änderungen und Druckfehler vorbehalten.
Phone: +46 31-69 53 00 Fax: +46 31-29 32 91 [email protected] www.calectro.se
0-10min
RW
0Pa to 2000Pa
RW
0Pa to 2000Pa
RW
1-2(*5)
RW
1-2(*5)
RW
0,1
RW
0-10V(*1,6)
RW
0,1
RW
0,1(*9)
RW
-100Pa to 2000PA
R
0-9(*7)
R