Calex PyroNFC Series Gebruikershandleiding - Pagina 4

Blader online of download pdf Gebruikershandleiding voor {categorie_naam} Calex PyroNFC Series. Calex PyroNFC Series 9 pagina's.

Calex PyroNFC Series Gebruikershandleiding

ELECTRICAL INTERFERENCE

To minimise electromagnetic interference or 'noise', the sensor should be mounted away from
motors, generators and such like.
WIRING
Check the distance between the sensor and the measurement instrumentation. If necessary,
the sensor can be ordered with a longer cable attached.

POWER SUPPLY

Check the supply voltage is between 6 V DC and 28 V DC.
To use the 0-10 V output, the supply voltage must be at least 12 V DC.
IMPORTANT: Ensure the power supply is only connected to the PWR+ and PWR- wires, and the
polarity is correct, before switching the power on.
Do not switch the power off and on again quickly. If the power is switched off, allow 15
seconds before switching it back on.

MECHANICAL INSTALLATION

All sensors come with a 1 metre cable and two mounting screws. The sensor can be mounted
on brackets or cut-outs of your own design, or you can use the fixed and adjustable mounting
bracket accessories which are shown below.
The supplied mounting screws are for use with a panel or bracket at least 2 mm thick. The
screws are 8 mm long.
Between the mounting holes, there must be a hole to allow the sensor a clear view through
the panel or bracket. This hole must be larger than the lens of the sensor or the aperture of
the air purge, if used. Use as large a hole as possible.
Note: The sensor must be grounded at only one point, either the cable shield or the mounting
screws, but not both.

MOUNTING BRACKETS

Fixed Mounting Bracket
Adjustable Mounting Bracket
15.0
4 x Mounting Holes Ø3.2
Ø13.5 Clearance
9.0
60°
49.0
49.0
33.5
31.0
31.0
50.0
24.0
9.0
60°
25.0
7.0
22.0
2 x Mounting Holes M4 Clearance
All dimensions in mm
4