Alderon Industries Versa'larm VA01D Bedienings-, onderhouds- en installatiehandleiding - Pagina 4
Blader online of download pdf Bedienings-, onderhouds- en installatiehandleiding voor {categorie_naam} Alderon Industries Versa'larm VA01D. Alderon Industries Versa'larm VA01D 4 pagina's. 1-zone alarm
Versa'larm
1-Zone Alarm - Model VA01D | Manual Silence
Operation, Maintenance and Installation Manual
Installation of the Alarm Panel Continued
7. Connect any combination of switches (rated 9 VDC, 200mA Minimum) such as a float switch, water sensor, or sump probe
sensor to Terminals C and 1 on the terminal block of the alarm panel. TERMINAL 2 IS NEVER USED. See below for wiring
examples (Fig. 13). The alarm is activated by a "closed" switch. CAUTION! - When installing the "Signaling Device", refer to
its installation instructions for proper installation.
TERMINALS C AND 1:
Float Switch
Black = 1
White = C
WaterSpotter™ or WaterSpotter™ Probe
Black = 1
Red = C
Combination of Sensors
Blacks = 1
Reds / Whites = C
Versa'larm
Accessory (P/N: 7933)
™
Indoor/Outdoor LED Strobe Beacon
Use 18 gauge wire and connect Red Wire
to Terminal C and Black Wire to Terminal 2
8. Plug the alarm panel power supply into a 120 VAC, 50/60 Hz standard
wall outlet and the green "Power" LED should illuminate (Fig. 14).
Testing the Alarm Panel
1. Test the alarm panel by pressing and holding the "Alarm Test" pushbutton
(Fig. 15) or activating the "Signaling Device" (i.e., float switch or water sensor
/ Fig. 16). The buzzer should annunciate and the alarm and silence LEDs
should illuminate. Slide the manual switch to the "S" (Silence) position (Fig.
17), this will silence the buzzer while the alarm and silence LEDs remain on.
After you remove pressure from the "Alarm Test" pushbutton or deactivate
the "Signaling Device" the alarm and silence LEDs will remain on until you
slide the manual switch to the "N" (Normal) position (Fig. 18). THE MANUAL
SILENCE SWITCH HAS TO BE IN THE "N" (NORMAL) POSITION FOR
THE "AUTO RESET" FEATURE TO REACTIVTE THE ALARM PANEL FOR
THE NEXT ALARM CYCLE (Fig. 18). If testing with "Signaling Device", make
sure to test all devices for complete system operation. Test product weekly to
ensure system integrity.
Alarm Systems
Control Panels
Alderon Industries - Hawley, MN | 218.483.3034 | [email protected] | alderonind.com
™
X
Float Switch
White = C
Black = 1
Float Switches
Leak Detection Systems
(Fig. 13)
X
Float Switch
WaterSpotter™
White = C
Red = C
Black = 1
Black = 1
(Fig. 15)
(Fig. 17)
N
S
X
Float Switch
White = C
Black = 1
WaterSpotter™
Red = C
WaterSpotter™ Probe
Black = 1
Red = C
Black = 1
(Fig. 14)
5 ft. Max
(Fig. 16)
(Fig. 18)
N
S