04 Setting the Heating Stages
Use the UP/DOWN keys to set 0, 1 or
2 stage.
Touch NEXT or ENTER.
05 Setting the Fan Operation
(Only displayed if GE selected)
Use the UP key to select "EL" for
electric operation where the
thermostat activates the indoor fan (G
terminal) during heating calls or
DOWN key to select GA for gas
operation where the equipment
plenum sensor activates the indoor
fan in heating calls.
Touch NEXT or ENTER.
06 Compressor Minimum Off Time
Use the UP/DOWN keys to change
the minimum off time (minutes) before
restarting the compressor.
Touch NEXT or ENTER.
Factory Default: 2 Minutes. Range: 0 to 9 Minutes
07 Heating Minimum Off Time
Use the UP/DOWN keys to change
the minimum off time (minutes) before
restarting a gas furnace or electric
strip heater.
Touch NEXT or ENTER.
Factory Default: 0 Minutes. Range: 0 to 9 Minutes
08 Minimum Run Time
Use the UP/DOWN keys to change
the minimum run time (minutes)
before turning a system off.
Touch NEXT or ENTER.
Factory Default: 2 Minutes. Range: 0 to 9 Minutes
09 Setting On-Off Temp Differential
Use the UP/DOWN keys to select 0,
1, 2.
Touch NEXT or ENTER.
o
Differential Mode0
0.5 On/Off Span.
o
Differential Mode1
1.0 On/Off Span.
o
Differential Mode2
1.5 On/Off Span.
Option
NEXT
ENTER
Factory Default: 1 Stage. Range: 0,1 or 2
Option
NEXT
ENTER
Factory Default: Gas. Range: GA or EL
Option
NEXT
ENTER
Option
NEXT
ENTER
Option
NEXT
ENTER
Option
NEXT
ENTER
Factory Default: #1. Range: 0, 1 or 2.
10 Smart Recovery
Smart recovery initiates a heating or cooling call so that the space is at temperature
when the setback period ends.
Use the UP key to select ON to turn
on smart recovery or the DOWN key
to select OF to turn smart recovery
off.
Touch NEXT or ENTER.
11 Vacant Heating Setpoint
Use the UP/DOWN keys to select the
heating temperature when the space
is vacant.
Touch NEXT or ENTER.
12 Vacant Cooling Setpoint
Use the
UP/DOWN
keys to
select the cooling temperature
when the space is vacant.
Touch
NEXT
or
ENTER.
13 Calibrate Living Area Temperature Sensor
Use the UP/DOWN keys to
change the Living area
temperature to the temperature
that the user feels is correct.
Touch NEXT or ENTER.
14 Calibrate Sleeping Area Temperature Sensor
Use the UP/DOWN keys to
change the Sleeping area
temperature to the temperature
that the user feels is correct.
Touch NEXT or ENTER
15 Airflow Update Time
This is the frequency, in minutes, that the damper position is updated.
Use the
UP/DOWN
keys to set
the time in minutes to update
the sleeping and living area
airflow.
Touch
NEXT
or
ENTER.
Factory Default: 2 Minutes. Range: 1 to 20 Minutes.
6
Option
NEXT
ENTER
Factory Default: Off. Range: On or Off.
Option
Heat
Vacant
NEXT
ENTER
o
o
Range: 44 F to 75 F
Factory Default: 65 F.
Option
Cool
Vacant
NEXT
ENTER
o
o
Factory Default: 80 F.
Range: 74 F to 95 F
Option
Living
NEXT
ENTER
Factory Default: None.
Range - +/-5
Option
Sleeping
NEXT
ENTER
Factory Default: None.
Range - +/-5
Option
NEXT
ENTER
o
o
o
o