ABB MPS-C 2000 Snelstarthandleiding - Pagina 3

Blader online of download pdf Snelstarthandleiding voor {categorie_naam} ABB MPS-C 2000. ABB MPS-C 2000 8 pagina's. Microprocessor-based protection and metering devices for low voltage power circuit breakers
Ook voor ABB MPS-C 2000: Gebruiksaanwijzing (18 pagina's)

Standard Features

Protection
MPSC-2000 is the first device to include Long Time, Short Time,
Instantaneous and Ground trip protection as standard functions, all with
user-selectable settings and curves. A single catalog number provides all
relay characteristics - no rating plugs are required.
MPSC-2000 protection functions are fully self-powered, taking tripping
energy from current conducted through the breaker without an auxiliary
Local and remote access to change relay settings and curves are
supply. The main memory module is non-volatile EEPROM, which stores
restricted to authorized personnel by password protection.
all protection settings and current values at the time of the last trip and
eliminates the need for battery backup.
Metering and Information
MPSC-2000 adds value well beyond the primary function of circuit
protection by providing a long list of breaker operational history
A bright red mechanical target indicates circuit breaker tripping.
The cause of trip can be determined by interrogation of the
device using the keypad and LCD display. The target resets
information as well as complete metering data with breakthrough accuracy
automatically when the unit is re-energized.
for a power circuit breaker trip device. Current and voltage measurements
are within 1% of breaker rating, and power indications are within 2% of
breaker rating.
MPSC-2000 provides user-friendly access to settings and metering data by
an on-screen menu with prompts. The large, easily readable LCD display is
also energy efficient. A 9-volt battery provides power for cold set-up and
A self-monitoring feature continuously monitors the condition
continuous LCD information display, even when the breaker is not closed
of the microprocessor. Normal operation is indicated by a red
LED on the front panel, flashing at the rate of once per
second. Any internal failure is signaled by a steady glow. The
and energized. The tactile touch keypad is impervious to contamination
LED blinks at the rate of 5 times per second to indicate Long
Time pickup, and continues to blink at this rate until reset or
from dust, moisture and lubricants.
until the breaker is tripped.
2