The maximum pressure drop of the combustion air piping is also 60 equivalent feet (30.5 m). See
Section 2.3. Note that this does NOT mean that the allowed combined pressure drop between the
vent and combustion air is 120 equivalent feet. That is, the vent cannot go above 60 equivalent
feet, even if the combustion air is less than 60 equivalent feet, and vice versa.
Example:
The vent system of two AM 1000 boilers (2 x 1,000,000 BTU/hr. = 2,000,000 BTU/hr.) consists of 30
foot length of vent pipe and 2 sharp 90° elbows. A termination cap is also installed. Each individual
vent connector consists of 5 ft. straight run and one WYE.
Common Vent pipe: 30 ft. + (2 x 10ft) + 5 ft. = 50 equivalent ft. (15.2 m)
Individual vent connector: 5 ft. + 5 ft. = 10 equivalent ft. (3.0 m)
Total Vent equivalent length: 50 ft. + 10 ft. = 60 (18.2 m)
60 equivalent ft.: OK to use 8" Common vent piping and 6" individual connectors.