TECHNICAL SPECIFICATIONS
Model
JPX1000RM
Capacity (VA)
Capacity (Watts)
Input
Input Voltage Range
Frequency
Output
On Battery Output Voltage
On Battery Output
Frequency
Overload Protection
AVR Function
Boost Function
Buck Function
Physical
Total # of UPS Receptacles
Maximum Dimensions
(H x D x W)
Battery
Sealed Maintenance Free
Lead Acid Battery
Typical Recharge Time
Warning Diagnostics
Indicators
Communication
Communication port
Environmental
Operating Temperature
Operating Relative Humidity
Management
Auto-Charger
Auto-Restart
TROUBLE SHOOTING
Problem
Possible Causes
Abnormal
1. AC Input missing
Mains normal but not
works in AC mode
2. Input Breaker is tripped
The on/off Button is
designed to prevent damage
by rapidly turning it off and
on.
The UPS will not turn on.
The unit is not connected to
an AC outlet.
The battery is worn out.
Mechanical problem.
Circuit breaker is tripped due
to overload
Outlets do not provide
power to equipment
Batteries are discharged
Unit has been damaged by a
surge or spike.
Site Fail:
Line and neutral conductors
Alarm code A01
of UPS Input are reversed or
the Ground is disconnected.
Battery low:
Alarm code A06
Battery capacity is low, UPS
will turn off soon
Overload:
Your equipment requires
Alarm code A14
more power than the UPS
can provide.
Alarm code A18
Over Temperature
JPX2000RM
1000VA
1920VA
600W
1200W
82V~148V
50/60Hz auto sensing
Pure Sine Wave at 120Vac +/-10%
50/60 Hz +/-1%
Yes
Yes
Yes
Nema 5-15R *8
88mm x 400mm x 433mm
24Vdc
8 Hours
LCD
USB,RS232
32F to 122F ( 0C to 40C )
0 to 90% NON-CONDENSING
Yes
Yes
Remedy
1. Check AC input connection.
2. Unplug the power cord of the UPS
then press the circuit breaker knob.
Turn the UPS off. Wait 10 seconds
and then turn the UPS on.
The unit must be connected to a
100-127V 50/60Hz outlet.
Contact technical support.
Turn the UPS off and unplug at least
one piece connected equipment.
Unplug the power cord of the UPS then
press the circuit breaker knob.
Allow the unit to recharge for at least 4
hours.
Contact technical support.
Check the input plug and socket.
1. Shut off non-essential equipment.
2. Save your data and turn off the
computer.
1. Shut off non-essential equipment.
1. Shut off non-essential equipment.
2. Check the fan for operation and if
the ventilation hole has been covered.
Fault
Output Short :
Fault code F09
Output circuit short.
Overload:
Your equipment requires
Fault code F14
more power than the UPS
can provide.
It will shutdown.
Fan fail :
Fault code F18
Fan has been damaged.
Fault code F19
Over Temperature
SOFTWARE DOWNLOAD
Power Master management software provides a user-friendly interface for your power systems. The
graphic user-interface is intuitive and displays essential power information at a glance. Please follow
procedure below to install the software.
Installation procedure:
1.
Download Power Master from the
website:
http://www.powermonitor.software/
2.
Double-click the file and follow the
installation steps.
When your computer restarts, the Power
Master software will appear as a blue
icon located in the system tray.
All rights reserved. Reproduction without permission is prohibited.
1. Shut down the UPS
2. Your attached equipment may have
problems, please remove them and
check again.
Shut off non-essential equipment. If
this solves the overload problem, the
UPS will transfer to normal operation.
1.Shut down the UPS
2.Replace the fan
1. Shut down the UPS. Restart the
UPS to Check the fan for operation
and if the ventilation hole has been
covered
2. Contact technical support for repair.