SmartPlate Application Guide for Boiler Interface
The non-AERCO boiler buffer tank sizing program will require the following inputs:
•
Boiler Model.
•
Water volume contained in a single boiler.
•
Quantity of boilers.
•
Boiler primary loop flow rate.
•
Boiler maximum supply temperature to SmartPlate.
•
Boiler Minimum Input.
•
Boiler Maximum Input.
•
Boiler Full Fire Efficiency.
•
Boiler Type. Choices include: condensing firetube, condensing cast aluminum, scotch
marine, all watertube, and all other boilers.
•
SmartPlate setpoint temperature.
•
SmartPlate model number.
•
Quantity of SmartPlates.
•
Domestic hot water building design load.
•
Building or Application Type. Choices include: elementary school, high school, hospital,
hotel, laundry, process, office building, prison, residential apartment, restaurant,
university building, and university dorm.
•
Pipe diameter and length to calculate piping volume.
•
Minimum flow per boiler - per the manufacturer's recommendation.
The SmartPlate system should be piped as a zone of the heating system utilizing non-AERCO
low mass boilers, as shown in Figure 8, below.