Set the LAN Type
Set the BAC/LON jumper for the type LAN in use: BAC for a BACnet network, LON for a L
Figure 11:
BAC/LON Jumper Set to the BAC (BACnet) Position when used with ECBSeries Controllers
Figure 12:
BAC/LON Jumper: Set to the LON (L
Setting Up an Allure EC-Smart-Vue Sensor Equipped with a Motion Sensor
The following procedure describes how to commission and test an Allure EC-Smart-Vue sensor equipped with a motion sensor as well as adjust the mo-
tion sensitivity (Allure EC-Smart-Vue M/-CM/-HM/-CHM sensors).
1. Connect an Allure EC-Smart-Vue sensor equipped with a motion sensor to the controller with a Cat 5e patch cable.
2. After a 30-second warm-up period, if movement is detected, the motion sensor light will turn on.
3. To test the sensor functionality, aim the sensor in the direction you want to detect motion and walk at a normal pace across the typical detection zone
and verify that the sensor light turns on. The light will turn on and after 2 seconds of non-movement, the motion sensor light will turn off.
4. Now to set the motion sensitivity, on the Allure EC-Smart-Vue sensor, press and hold the Menu button
menu. 10000 is shown on the display.
5. Press the down button
6. Press the Menu button
Network Type
Jumper
Network Type
Jumper
W
ON
Screen Timeout: 15 seconds
to set the number to 9995 (this is the default password).
Screen Timeout: 15 seconds
to submit the password. Upon submitting the password, the GEN CFG menu appears on the display.
Screen Timeout: 30 seconds
ON
BAC
LON
3.5 mm (1/8") Network
Access Jack
BAC
LON
3.5 mm (1/8") Network
Access Jack
) Position when used with ECL Series Controllers
ORKS
OR
OR
OR
W
network.
ORKS
for 5 seconds to enter the password
11 / 16